7 Specifications

7.1 Electrical Data

7.1.1 Mains Supply 3x200–240 V AC
Type designation
1)
Overload
Typical shaft output [kW]
Typical shaft output [hp] at 208 V
IP20/chassis
6)
IP55/NEMA 12
IP66/NEMA 4X
Output current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
Continuous kVA (208 V AC) [kVA]
Maximum input current
Continuous (3x200–240 V) [A]
Intermittent (3x200–240 V) [A]
More specifications
3)
Estimated power loss
at rated maximum load [W]
IP20, IP21 maximum cable cross-section
2
load sharing) [mm
/(AWG)]
IP55, IP66 maximum cable cross-section
2
load sharing) [mm
/(AWG)]
Maximum cable cross-section with disconnect
5)
Efficiency
Table 7.1 Mains Supply 3x200–240 V AC
MG16G202
Design Guide
4)
2)
(mains, motor, brake, and
2)
(mains, motor, brake, and
Danfoss A/S © 08/2015 All rights reserved.
P1K1
P1K5
P2K2
NO
NO
NO
1.1
1.5
2.2
1.5
2.0
2.9
A2
A2
A2
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
A4/A5
6.6
7.5
10.6
7.3
8.3
11.7
2.38
2.70
3.82
5.9
6.8
9.5
6.5
7.5
10.5
63
82
116
4, 4, 4 (12, 12, 12)
(minimum 0.2 (24))
4, 4, 4 (12, 12, 12)
6, 4, 4 (10, 12, 12)
0.96
0.96
0.96
P3K0
P3K7
NO
NO
3.0
3.7
4.0
4.9
A3
A3
A5
A5
A5
A5
12.5
16.7
7
13.8
18.4
4.50
6.00
11.3
15.0
12.4
16.5
155
185
0.96
0.96
115
7