Harmonics - Danfoss VLT Refrigeration Drive FC 103 Design Manual

1.1-90 kw
Hide thumbs Also See for VLT Refrigeration Drive FC 103:
Table of Contents

Advertisement

System Integration
of the machine. This can be difficult for
pumps.
2f
Make a direct ground connection
between the motor and motor load (for
example pump).
3.
Lower the IGBT switching frequency.
4.
Modify the inverter waveform, 60° AVM vs.
SFAVM.
5.
Install a shaft grounding system or use an
isolating coupling.
6.
Apply conductive lubrication.
7.
Use minimum speed settings if possible.
8.
Try to ensure that the mains voltage is balanced
to ground. This can be difficult for IT, TT, TN-CS,
or Grounded leg systems.
9.
Use a dU/dt or sine-wave filter.

3.2.7 Harmonics

Electrical devices with diode rectifiers, such as
Fluorescent lights
Computers
Copiers
Fax machines
Various laboratory equipment, and
Telecommunications systems
can add harmonic distortion to a mains supply. Frequency
converters use a diode bridge input, which can also
contribute to harmonic distortion.
The frequency converter does not draw current uniformly
from the power line. This non-sinusoidal current has
components that are multiples of the fundamental current
frequency. These components are referred to as harmonics.
It is important to control the total harmonic distortion on
the mains supply. Although the harmonic currents do not
directly affect electrical energy consumption, they generate
heat in wiring and transformers. This heat generation can
affect other devices on the same power line.
3.2.7.1 Harmonic Analysis
Various characteristics of a building's electrical system
determine the exact harmonic contribution of the
frequency converter to the THD of a facility and its ability
to meet IEEE standards. Generalisations about the
harmonic contribution of frequency converters on a
specific facility is difficult. When necessary, perform an
analysis of the system harmonics to determine equipment
effects.
MG16G202
Design Guide
A frequency converter takes up a non-sinusoidal current
from mains, which increases the input current I
sinusoidal current is transformed with a Fourier series
analysis and split up into sine-wave currents with different
frequencies, that is, different harmonic currents I
50 Hz or 60 Hz as the fundamental frequency.
The harmonics do not affect the power consumption
directly, but increase the heat losses in the installation
(transformer, inductors, cables). So, in power plants with a
high percentage of rectifier load, keep harmonic currents
at a low level to avoid overload of the transformer,
inductors, and cables.
Abbreviation
f
1
I
1
U
1
I
n
U
n
n
Table 3.9 Harmonics-related Abbreviations
Current
Frequency
[Hz]
Table 3.10 Transformed Non-sinusoidal Current
Current
Input current
Table 3.11 Harmonic Currents Compared to the RMS Input
Current
Illustration 3.3 DC-link Coils
NOTICE
Some of the harmonic currents can disturb communi-
cation equipment connected to the same transformer or
cause resonance with power factor correction capacitors.
To ensure low harmonic currents, the frequency converter
is equipped with passive filters. DC-coils reduce the total
harmonic distortion (THD) to 40%.
The voltage distortion on the mains supply voltage
depends on the size of the harmonic currents multiplied
by the mains impedance for the frequency in question. The
Danfoss A/S © 08/2015 All rights reserved.
Description
Fundamental frequency
Fundamental current
Fundamental voltage
Harmonic currents
Harmonic voltage
Harmonic order
Fundamental
Harmonic current (I
current (I
)
1
I
I
I
1
5
7
50
250
350
Harmonic current
I
I
I
RMS
1
5
1.0
0.9
0.4
. A non-
RMS
with
N
3
3
)
n
I
11
550
I
I
7
11-49
0.2
< 0.1
45

Advertisement

Table of Contents
loading

Table of Contents