Emc Test Results (Emission) - Danfoss VLT Refrigeration Drive FC 103 Design Manual

1.1-90 kw
Hide thumbs Also See for VLT Refrigeration Drive FC 103:
Table of Contents

Advertisement

System Integration

3.2.2 EMC Test Results (Emission)

The following test results have been obtained using a system with a frequency converter (with options if relevant), a
screened control cable, a control box with potentiometer, as well as a motor and motor screened cable.
3
3
RFI filter type
Standards
and
requirements
H1
1.1–22 kW 220–240 V
1.1–45 kW 200–240 V
1.1–90 kW 380–480 V
H2/H5
1.1–22 kW 220–240 V
1.1–3.7 kW 200–240 V
5.5–45 kW 200–240 V
1.1–7.5 kW 380–480 V
11–90 kW 380–480 V
HX
1.1–90 kW 525–600 V
Table 3.4 EMC Test Results (Emission)
HX, H1 or H2 is defined in the type code pos. 16–17 for EMC filters.
HX – No EMC filters built in the frequency converter (600 V units only).
H1 – Integrated EMC filter. Fulfil Class A1/B.
H2 – No additional EMC filter. Fulfil Class A2.
H5 – Marine versions. Fulfil same emissions levels as H2 versions.
42
VLT
EN 55011
Class B
Housing, trades,
and light
industries
EN/IEC 61800-3
Category C1
First environ-
ment Home
and office
50
50
50
No
No
No
No
No
No
Danfoss A/S © 08/2015 All rights reserved.
®
Refrigeration Drive FC 103
Conducted emission
Cable length [m]
Class A Group
Class A Group 2
1
Industrial
Industrial
environ-
environ-
ment
ment
Category C2
Category C3
First environ-
Second environ-
ment Home
ment Industrial
and office
150
150
150
150
150
150
No
25
No
5
No
25
No
5
No
25
No
No
Radiated emission
Cable length [m]
Class B
Class A Group
Housing, trades,
1
and light
Industrial
industries
environment
Category C1
Category C2
First
First
environment
environment
Home and
Home and
office
office
No
Yes
No
Yes
No
Yes
No
No
No
No
No
No
No
No
No
No
No
No
Class A Group
2
Industrial
environment
Category C3
Second
environment
Industrial
N/A
Yes
Yes
N/A
No
No
No
No
No
MG16G202

Advertisement

Table of Contents
loading