Danfoss VLT Refrigeration Drive FC 103 Design Manual page 130

1.1-90 kw
Hide thumbs Also See for VLT Refrigeration Drive FC 103:
Table of Contents

Advertisement

Specifications
380–480 V
Enclosure
type
A2
A3
B3
B4
C3
C4
A4
A5
7
7
B1
B2
C1
C2
Table 7.10 380–480 V, Enclosure Types A, B, and C
525–600 V
Enclosure
type
A3
B3
B4
C3
C4
A5
B1
B2
C1
C2
Table 7.11 525–600 V, Enclosure Types A, B, and C
128
Power [kW]
Recommended
fuse size
1.1–4.0
gG-10 (1.1–3)
gG-16 (4)
5.5–7.5
gG-16
11–18
gG-40
22–37
gG-50 (22)
gG-63 (30)
gG-80 (37)
45–55
gG-100 (45)
gG-160 (55)
75–90
aR-200 (75)
aR-250 (90)
1.1–4
gG-10 (1.1–3)
gG-16 (4)
1.1–7.5
gG-10 (1.1–3)
gG-16 (4–7.5)
11–18.5
gG-40
22–30
gG-50 (22)
gG-63 (30)
37–55
gG-80 (37)
gG-100 (45)
gG-160 (55)
75–90
aR-200 (75)
aR-250 (90)
Power [kW]
Recommended
fuse size
5.5–7.5
gG-10 (5.5)
gG-16 (7.5)
11–18
gG-25 (11)
gG-32 (15–18)
22–37
gG-40 (22)
gG-50 (30)
gG-63 (37)
45–55
gG-63 (45)
gG-100 (55)
75–90
aR-160 (75)
aR-200 (90)
1.1–7.5
gG-10 (1.1–5.5)
gG-16 (7.5)
11–18
gG-25 (11)
gG-32 (15)
gG-40 (18.5)
22–30
gG-50 (22)
gG-63 (30)
37–55
gG-63 (37)
gG-100 (45)
aR-160 (55)
75–90
aR-200 (75–90)
Danfoss A/S © 08/2015 All rights reserved.
®
VLT
Refrigeration Drive FC 103
Recommended
maximum fuse size
gG-25
gG-32
gG-63
gG-125
gG-150 (45)
gG-160 (55)
aR-250
gG-32
gG-32
gG-80
gG-100
gG-160
aR-250
Recommended
maximum fuse size
gG-32
gG-63
gG-125
gG-150
aR-250
gG-32
gG-80
gG-100
gG-160 (37–45)
aR-250 (55)
aR-250
Recommended circuit
Maximum trip level
breaker (Moeller)
PKZM0-25
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
Recommended circuit
Maximum trip level
breaker (Moeller)
PKZM0-25
PKZM4-50
NZMB1-A100
NZMB2-A200
NZMB2-A250
PKZM0-25
PKZM4-63
NZMB1-A100
NZMB2-A200
NZMB2-A250
[A]
25
25
50
100
150
250
25
25
63
100
160
250
[A]
25
50
100
150
250
25
63
100
160
250
MG16G202