Device Description
Table 15: Technical Data – Data Contacts
Data contacts
Pos : 20.31 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Klimatisc he U mgebungsbeding ungen/T ec hnische D aten Kli mat. U mgebungsbed. ohne erw. T emp. 0...55°C/- 25...+ 85°C @ 5\mod_1247657968368_21.doc x @ 37603 @ 3 @ 1
3.6.6

Climatic Environmental Conditions

Table 16: Technical Data – Climatic Environmental Conditions
Operating temperature range
Storage temperature range
Relative humidity without condensation Max. 95 %
Resistance to harmful substances
Maximum pollutant concentration at
relative humidity < 75 %
Special conditions
Pos : 20.32 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Slide contact, hard gold plated, self-
cleaning
0 °C ... 55 °C
−25 °C ... +85 °C
Acc. to IEC 60068-2-42 and
IEC 60068-2-43
SO
≤ 25 ppm
2
H
S ≤ 10 ppm
2
Ensure that additional measures for
components are taken, which are used in
an environment involving:
– dust, caustic vapors or gases
– ionizing radiation