Display Elements; Figure 5: Display Elements; Table :8 Legend For The "Display Elements" Figure - WAGO 750-496 Manual

8ai 0/4-20ma s.e. 8-channel analog input module 0/4-20 ma, singleended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Pos : 20.19 /Alle Serien (Allgemeine M odul e)/Übersc hriften/Ebene 2/Anz eigeelemente - Ü bersc hrift 2 @ 4\mod_1240984390875_21.doc x @ 31964 @ 2 @ 1
3.3

Display Elements

Pos : 20.20 /Serie 750 ( WAGO-I/O-SYST EM)/Gerätebeschr eibung/Anzeig eel emente/Anal ogeing angs kl emmen/Anz eigeelemente 750-0496 @ 22\mod_1426173734344_21.doc x @ 177614 @ @ 1

Figure 5: Display Elements

Table :8 Legend for the "Display Elements" Figure

Chann
el
1
2
3
4
5
6
7
8
Pos : 20.21 /D okumentati on allgemei n/Gli ederungsel emente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc x @ 21810 @ @ 1
Manual
Version 1.2.0
Designation
LED
Function AI1
1
Error AI1
9
Function AI2
2
Error AI2
10
Function AI3
3
Error AI3
11
Function AI4
4
Error AI4
12
Function AI5
5
Error AI5
13
Function AI6
6
Error AI6
14
Function AI7
7
Error AI7
15
Function AI8
8
Error AI8
16
State
Not ready for operation or no/faulty
OFF
internal bus communication, channel
deactivated
Ready for operation and undisturbed
Green
internal bus communication
No error and/or diagnostics deactivated,
OFF
or channel deactivated
Permissible measurement range
overrange and underrange, short circuit,
general error
Red
Wire break (sensor type 4 ... 20 mA
and 3.6 ... 21 mA only)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
(see Channel 1)
Device Description
Function
21

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents