Inputs

Table 12: Technical Data – Inputs
Number of inputs
Connection types
Sensor connection
Signal current
(configurable)
Input resistance
Configurable
software input filter
Dielectric strength
Resolution of the A/D converter
Conversion method
Conversion time
Resolution of measured value
Measuring error at 25 °C
Temperature coefficient
Diagnostics
Signaling with diagnostics
Pos : 20.30.1 /Alle Serien (Allgemeine M odul e)/Übersc hriften/Ebene 3/Ans chl usstec hni k - Übersc hrift 3 @ 17\mod_1380123271324_21.doc x @ 132788 @ 3 @ 1
3.6.5

Connection Type

Pos : 20.30.2 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Ansc hl usstec hni k/Technisc he Daten Ver drahtungs ebene Pus h-in CC - 0,08 bis 1,5mm2( eindrg.) + 0,25 bis 1,5mm2( fei ndrg.) @ 19\mod_1400241224524_21.doc x @ 153913 @ @ 1
Table 13: Technical Data ‒ Field Wiring
Wire connection
Cross section, solid wire
Cross section, fine-stranded wire
Stripped lengths
Pos : 20.30.3 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Ansc hl usstec hni k/Technisc he Daten Leis tungs kontakte (Mess er/F eder) @ 19\mod_1400241643293_21.doc x @ 153921 @ @ 1
Table 14: Technical Data – Power Jumper Contacts
Power jumper contacts
Pos : 20.30.4 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Tec hnische D aten/Ansc hl usstec hni k/Technisc he Daten D atenkontakte @ 17\mod_1380123495844_21.doc x @ 132794 @ @ 1
Manual
Version 1.2.0
typ.
max.
(without filter)
typ.
per channel ≤ 1.25 ms
per module ≤ 10 ms
Device Description
8
Single-ended
2-conductor connection
0 ... +20 mA
+4 ... +20 mA
+3.6 ... +21 mA
≤ 200 Ω
Bessel filter 2nd order f
31.2 VDC
14 bits
SAR
(Successive Approximation Register)
12 bits + 1 bit sign
< ±0.1% of full scale value
< ±0.01% /K of full scale value
Measurement range underflow
Measurement range overflow
Short circuit
General error
Wire break
(sensor type 4 ... 20 mA and
3.6 ... 21 mA only)
Process image
Status byte
LED
Push-in CAGE CLAMP
0.08 mm² ... 1.5 mm² / AWG 28 ... 16
0.25 mm² ... 1.5 mm² / AWG 22 ... 16
8 mm ... 9 mm / 0.33 in
Blade/spring contact, self-cleaning
25