Sensor Type 4; Table 20: Process Image, Sensor Type 4 - WAGO 750-496 Manual

8ai 0/4-20ma s.e. 8-channel analog input module 0/4-20 ma, singleended
Hide thumbs Also See for 750-496:
Table of Contents

Advertisement

34
Process Image
4.3.2.2
Sensor Type 4 ... 20 mA
For the current measurement with sensor type 4 ... 20 mA, the input range of
4 ... +20 mA is mapped to a value rage of 0 ... +32767. The current underranges
and overranges refer to manufacturer range violations.
Table 20: Process Image, Sensor Type 4 ... 20 mA, Two's Complement Representation
Input current
mA
< 1.0
Wire break
< 4.0
Underrange
4.0
5.6
7.2
8.8
10.4
12.0
13.6
15.2
16.8
18.4
20.0
Overrange
> 20.0
Short circuit
> 21.0
1) Status bits: X: not used, F= error, Ü= overflow
2) When underrange / overrange limit is ON
3) When wire break / short circuit diagnostics is ON
Numeric value
Binary
'0000.0000.0000.0 011'
3)
'0000.0000.0000.0 011'
2)
'0000.0000.0000.0 000'
'0000.1100.1100.0 000'
'0001.1001.1001.1 000'
'0010.0110.0110.0 000'
'0011.0011.0011.0 000'
'0011.1111.1111.1 000'
'0100.1100.1100.1 000'
'0101.1001.1001.1 000'
'0110.0110.0110.0 000'
'0111.0011.0011.0 000'
'0111.1111.1111.1 000'
2)
'0111.1111.1111.1 011'
3)
'0111.1111.1111.1 011'
1)
XFÜ
Hex.
Dec.
0x0003
3
0x0003
3
0x0000
0
0x0CC8
3272
0x1998
6552
0x2660
9824
0x3330
13104
0x3FF8
16376
0x4CC8
19656
0x5998
22936
0x6660
26208
0x7330
29488
0x7FF8
32760
0x7FFB
32763
0x7FFB
32763
WAGO-I/O-SYSTEM 750
750-496 8AI 0/4-20mA S.E.
Status
Byte
Error LED
Hex.
0x60
ON
0x41
ON
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x00
OFF
0x42
ON
0x50
ON
Manual
Version 1.2.0

Hide quick links:

Advertisement

Chapters

Table of Contents
loading

Table of Contents