VERTIV INTELLIGENT RACK PDU
Page 89
5.5.10.
SN MP
Simple Network Management Protocol (SNMP) can be used to monitor the unit's measurements and sta-
tus, if desired. SNMP v1, v2c and v3 are supported. In addition, alarm traps can be sent to up to two IP
addresses.
Figure 3-53 SNMP Configuration Page
The SNMP-V1/V2c and SNMP-V3 Service can be enabled or disabled independently as desired. The
service will normally listen for data-read requests (a.k.a. "GET requests") on Port 161, which is the usual
default for SNMP services; this can also be changed if desired.
The Management Information Base (MIB) can be downloaded from the unit, if needed, via the MIB link at
the top of the web page. Clicking this link will download a .ZIP archive containing both the MIB file itself,
and a CSV-formatted spreadsheet describing the available OIDs in a human-readable form to assist you
in setting up your SNMP manager to read data from the unit.
Figure 3-54 SNMP Users Configuration Page
The Users section allows you to configure the various Read, Write, and Trap communities for
SNMP services. You can also configure the authentication types and encryption methods used
for the SNMP v3 if desired. Click the Modify icon to change settings.
Figure 3-55 SNMP Traps Configuration Page
Traps allow you to define the trap destination IP address, the trap port number and the type of SNMP trap
to be used.