To add a new Alarm or Warning Event:
1.
Click the Add/Modify Alarms & W arnings button:
2.
Set the desired conditions for this Event as follows:
a.
Select the Name of the phase or circuit you wish to set an Event on.
b.
Select the measurement (current, voltage, etc.) you want to Trigger the Event.
c.
Set the Severity level ("Warning", or "Alarm") for this Event.
d.
Select the threshold Type, "Status" (trips if device status changes), "high" (trips if the measurement
goes above the threshold) or "low" (trips if the measurement goes below the threshold).
e.
Type in the desired Threshold Value (any number between -999.0 ~ 999.0 is valid).
f.
Type in the desired Clear Delay time in seconds. Any value other than "0" means that once this
Event is tripped, the measurement must return to normal for this many seconds before the Event
will clear and reset. Clear Delay can be up to 14400 seconds (4 hours).
g.
Type in the desired Trip Delay time in seconds. Any value other than "0" means that the measure-
ment must exceed the threshold for this many seconds before the Event will be tripped. Trip Delay
can be up to 14400 seconds (4 hours).
h.
Latching Mode: If enabled, this Event and its associated Actions remain active until the Event is
acknowledged, even if the measurement subsequently returns to normal.
i.
Valid Time decides when an Alarm notification can be sent. Valid Time is set by clicking the
Add/Modify icon and setting the days and time ranges notifications will be sent. Then clicking Save.
Figure 3-21 Add/Modify Alarms & Warnings Page