VERTIV INTELLIGENT RACK PDU
3.1.2. ENVIRON ME NT AL
The operational environmental limits pertaining to Temperature, Humidity and Elevation are as
defined below.

3.1.2.1. TEMPERATURE

Operating
Storage

3.1.2.2. HUMIDITY

Table 1-3
Operating
Storage

3.1.2.3. ELEVATION

Table 1-4
Operating
Storage
3.1.3. ELECT RIC AL
Electrical product characteristics an performance are defined below. Also, please see the prod-
uct nameplate for additional rating limits.
Table 1-2
Minimum
10°C (50°F)
-25°C (-13°F)
Humidity Limits
Minimun
5%
5%
Elevation Limits
Minimun
0 m (0 ft)
0 m (0 ft)
Temperature Limits
Maximum
60°C (140°F) UL Listed Models
50°C (122°F) CE Marked Models
65°C (149°F)
Maximum
95% (non-condensing)
95% (non-condensing)
Maximum
3,200 m (10,500 ft)
15,240 m (50,000 ft)