5.5.6. DISPL AY
The unit's local display settings can be changed via the Display tab of the System menu.
The Display Mode section allows the user to configure what measurements are scrolling on the local dis-
play.
1.
Current mode will scroll all current measurements in Amps for Total, Phases and Circuits on the local

display.

2.
Total Power mode will display the Total Power in kilo-watts on the local display.
a.
<10kW will be displayed as n.nn
b.
>10kW will be displayed as nn.n
3.
Current & Total Power mode will display both Current in Amps and Total Power as indicated above.
4.
Click the Save button after making Display Mode selection.
The VLC Mode section allows the user to configure what measurements are scrolling on the local display.
1.
Select Enable to turn on VLC mode. Refer to the Interchangeable Monitoring Device section for more
information on VLC.
2.
Select Disable to turn off VLC mode and return to the currently configured Display Mode.
NOTE: VLC can also be Enabled/Disabled by using a button press sequence on the local display. VLC
Mode cannot be permanently disabled.
Figure 3-46 Display Mode
Figure 3-47 VLC Mode