Sungrow SG2K5-S User Manual page 54

Pv grid-connected inverter
Hide thumbs Also See for SG2K5-S:
Table of Contents

Advertisement

7 LCD Operation
Tab. 7-4 Default Parameters for Grid Standards
Other
Parameter
(Default)
V
(V)
253.0
max-rec
V
(V)
205.0
min-rec
10-Minute Over-voltage Protection
ON: enables the protection function by default. The
inverter will automatically disconnect from the grid
within 3 s when the average voltage for a 10 min
period exceeds the set-point of 10 Min Over Vtg.
OFF: disables the function.
Range: 244.0 V–258.0 V
The default value of 10 Min Vtg is 248.0 V for New Zealand (code "NZ"). Refer
to the following table for different grid standards in Australia.
Other
Parameter
(Default)
10 Min Vtg
255.0
Volt-watt Response
The Volt-watt response mode is enabled by default.
Set four grid voltage reference values. The output power of the inverter will vary
in response to the grid voltages.
OFF
Tab. 7-5 "Volt-watt" Mode Parameter Explanations
Parameter
Explanation
Grid
V1 Ref.
value 1
Grid
V2 Ref.
value 2
Grid
V3 Ref.
value 3
Grid
V4 Ref.
value 4
The response curve is defined by the voltage reference values and
corresponding power levels.
46
AG
EE
253.0
253.0
205.0
182.0
AG
EE
255.0
255.0
V1 Ref.:
ON
voltage
reference
voltage
reference
voltage
reference
voltage
reference
EG
PN
253.0
253.0
182.0
205.0
EG
PN
257.0
258.0
207.0V
V2 Ref.:
220.0V
Default
AU
NZ
207.0 V
207.0 V
220.0 V
220.0 V
250.0 V
244.0 V
265.0 V
255.0 V
User Manual
PC
WP
253.0
253.0
205.0
205.0
ON
OFF
10 Min Vtg:
255.0V
PC
WP
255.0
258.0
V3 Ref.:
250.0V
V4 Ref.:
265.0V
Range
Not
applicable
216 V–230 V
235 V–255 V
244 V–265 V