If the protection function is triggered, the inverter will automatically disconnect
from the grid with the "Error xxx" state displayed on the LCD main screen. After
the grid voltage or frequency recovers to the specified range, the inverter will
start running normally and can reconnect to the grid.
Touch ESC to choose the item and press ENT to enter the setting interface.
Single/Mul Prot.
Prot. Recover
Single/Multiple Protection
Touch ESC to change the value and touch ENT to move the cursor.
Confirm settings by pressing ENT.
Confirm settings and scroll pages by pressing ENT.
Single stage
Multi. stage
Tab. 7-3 Protective Parameters and the Range
Parameter
V
max
V
min
1-V
max
2-V
max
1-V
min
2-V
min
* Refer to Tab. 7-7 for the default values of the parameters.
Too high grid voltage may affect the normal usage and the life of
household loads. The loss of any or all the warranty rights may follow if
the protection set-point is beyond the specified range.
Protection Recover
Vmax-rec (230.0 V–277.0 V):
Recovery value for over-voltage error. Inverter will start
operating when the grid voltage falls below this value.
Vmin-rec (179.0 V–230.0 V):
Recovery value for under-voltage error. Inverter will start
operating when the grid voltage is above this value.
10 Min Over Vtg En.
Volt-watt
Vmax:
Vmin:
1-Vmax:
2-Vmax:
Explanation
Grid over-voltage
Grid under-voltage
Grid over-voltage 1 (V>)
Grid over-voltage 2 (V>>)
Grid under-voltage 1 (V<)
Grid under–voltage 2 (V<<)
Grid Prot. Adj.
260.0V
180.0V
260.0V
1-Vmin:
2-Vmin:
265.0V
Range
230.0 V–277.0 V
179.0 V–230.0 V
230.0 V–277.0 V
230.0 V–277.0 V
179.0 V–230.0 V
179.0 V–230.0 V
7 LCD Operation
180.0V
180.0V
Vmax-rec: 253.0V
Vmin-rec: 205.0V