6.3 Special Conditions
6.3.1 Derating for Ambient Temperature
and Switching Frequency
The ambient temperature measured over 24 hours should
be at least 5 °C (9° F) lower than the maximum ambient
temperature that is specified for the adjustable frequency
driver. If the adjustable frequency drive is operated at a
high ambient temperature, the continuous output current
should be decreased. For derating curve, see VLT
Basic Drive Design Guide.
6
6
6.3.2 Derating for Low Air Pressure and
High Altitudes
The cooling capability of air is decreased at low air
pressure. For altitudes above 2000 m (6562 ft), contact
Danfoss regarding PELV. Below 1000 m (3281 ft) altitude,
no derating is necessary. Above 1000 m (3281 ft), the
ambient temperature or the maximum output current
should be decreased. Decrease the output by 1 % per
100 m (328 ft) altitude above 1000 m (3281 ft) or reduce
the maximum ambient temperature by 1 °C per 200 m
(656 ft).