Product Specifications; Model Number; Idc Input; Idc Output - Eaton 9390 Installation And Operation Manual

40–80 kva ups, integrated distribution cabinet
Hide thumbs Also See for 9390:
Table of Contents

Advertisement

Chapter 7

Product Specifications

The following sections detail the input, output, and environmental specifications for the Integrated Distribution
Cabinet (IDC).
7.1

Model Number

The IDC is housed in a free–standing cabinet with safety shields behind the doors.
System
Eaton 9390
7.2

IDC Input

Operating Input Voltage
(Nominal +10/–15%)
Operating Input Frequency Range ±5 Hz
Operating Input Current
7.3

IDC Output

Operating Output Voltage
(Nominal +10/15%)
Operating Output Frequency
Range
Output Current
7.4

Environmental Specifications

Operating Temperature
Operating Altitude
Storage Temperature
Relative Humidity (operating and
storage)
Acoustical Noise
EMI Suppression
Electrostatic Discharge (ESD)
Immunity
480 Vac nominal (432–504 Vac) at 60 Hz
See Table D or Table E starting on page 9-12
208 Vac nominal (60 Hz)
480 Vac nominal (60 Hz)
5 Hz
See Table D or Table E starting on page 9-12
0 to 40C (32 to 104F) without derating. The recommended operating
temperature is 25C (77F).
Maximum 1500m (5000 ft) at 40C (104F) without derating
-25 to 60C (-13 to 140F)
5% to 95% maximum noncondensing
N/A
N/A
N/A
Eaton 9390 IDC (40–80 kVA) Installation and Operation Manual 164201690 Rev 3 www.eaton.com/powerquality
Model
Frequency
40–80 kVA
60 Hz
7-1