6
Assembly and installation
6.1 Scope of delivery
Tab. 3: The following components are included as standard:
Description
Measuring/control system DULCOMARIN
Assembly material, complete, 2P universal (set).
Threaded cable connector set, M20 DCPa.
Data DVD.
Operating instructions.
Access card with PUK.
User qualification, mechanical installation: trained and qualified
n
Ä Chapter 1.5 'User qualification' on page 10
personnel
User qualification, electrical installation: electrical technician
n
Ä Chapter 1.5 'User qualification' on page 10
NOTICE!
Installation site and ambient conditions
–
The controller meets the requirements for IP 67
(housing, closed) or IP 20 (housing, open) and
leak-tightness (based on NEMA 4X). These
standards are only met if all seals and
threaded connectors are correctly fitted.
–
Only carry out the (electrical) installation after
(mechanical) installation.
–
Ensure that there is unimpeded access for
operation.
–
Ensure safe and low-vibration fixing.
–
No direct sunlight.
–
Permissible ambient temperature of the con‐
troller at the installation location: - 5 ... 50 °C at
max. 95% relative air humidity (non-con‐
densing).
–
Requires a low voltage cable with a tempera‐
ture resistance of ≧ 70 °C.
–
Take into consideration the permissible
ambient temperature of the connected sensors
and other components.
–
The controller is only suitable for operation in
closed rooms. If operating outdoors, use a suit‐
able protective enclosure to protect the con‐
troller from the environment.
Mounting position
–
As standard, a wall-mounted controller is used.
Always install the controller so that the cable
–
entries point downwards.
Leave sufficient free space for the cables.
–
®
3 including wall bracket.
Assembly and installation
Quantity
1
2
1
1
1
1
31