Factory Settings Of Device; Factory Settings For Free Chlorine Measured Variable - ProMinent DULCOMARIN 3 Compact Assembly And Operating Instructions Manual

Multi-channel measuring and control system
Table of Contents

Advertisement

Factory settings of device

13
Factory settings of device
13.1

Factory settings for free chlorine measured variable

Free chlorine measured variable - factory settings
Name
Controller
Control param‐
settings
eter
Control type
Control direction
Setpoint
Display range
(bar graph)
Limit values
(advance
warning)
Limit values
(advance
warning)
Alarms (alarm
relay switches)
Alarms (alarm
relay switches
and control stops)
Time for which
limit value is
exceeded, range
1 ... 1800 s
Recorder 2 h
Recorder
* After superchlorination the alarms must be suppressed until normal mode is re-established.
Superchlorination lasts up to 8 hours.
94
Normal mode
active
PID
Increase value, on
one side
0.5 ppm
Xp
0.2 ppm
Ti
0 s (P) 3000 s (PI/
PID)
Td
0 s (P/PI/PID)
min.
0
max.
1
min.
0.3
max.
0.7
min.
0.3
max.
0.8
300 s
min.
dynamic
max.
dynamic
min.
0
max.
2
Superchlorination
Eco!Mode
®
inactive
inactive
PID
PID
Increase value, on
Increase value, on
one side
one side
0.5 ppm
10 ppm
2 ppm
0.5 ppm
0 s (P) 3000 s (PI/
0 s (P) 3000 s (PI/
PID)
PID)
0 s (P/PI/PID)
0 s (P/PI/PID)
0
0
1
8
0.3
0.3
0.7
4.2
0.3
0.3
0.8
--
300 s
dynamic
dynamic
dynamic
dynamic
0
0
2
10
*