Factory Settings; Switching On The Power Supply; Parameterization Via The "Easy Setup" Menu Function - ABB ProcessMaster FEP611 Operating Instructions Manual

Table of Contents

Advertisement

6.5

Factory settings

The device can be factory parameterized to customer
specifications upon request. If no customer information is
available, the device is delivered with factory settings.
Parameter
Qv Max 1
Sensor Tag
TX Location TAG
Unit Volumeflow Qv
Unit Vol. Totalizer
Pulses per Unit
Pulse Width
Damping
Digital output 41 / 42
Digital output 51 / 52
Current output
Curr.Out at Alarm
Current at flowrate > 20.5 mA
Low Flow Cut Off
EPD Alarm
6.6

Switching on the power supply

— Switch on the power supply.
The LCD display shows the following display during the
startup process:
System Startup
Processing
The process display is displayed after the startup process.
34 OI/FEP610/FEH610-EN Rev. B | ProcessMaster FEP610, HygienicMaster FEH610
Factory setting
Q
DN (see table in chapter
max
"Measuring range table" on page 37)
None
None
l/min
l (liter)
1
100 ms
1 s
Impulse für Forward & Reverse
Flow Direction
4-20mA FWD/REV
High Alarm, 21.8 mA
Off
1 %
Off
6.7

Parameterization via the "Easy Setup" menu function

Settings for the most common parameters are summarized in
the "Easy Setup" menu. This menu provides the fastest way to
configure the device.
The following section describes parameterization via the "Easy
Setup" menu function.
Process Display
Q
0.00
∑+
0000.00
∑-
0000.00
1. Use
to switch to the configuration level.
Access Level
Read Only
Standard
Back
Select
2. Use
/
to select "Standard".
3. Confirm the selection with
Enter Password
**********
RSTUVWXYZ 12345
Next
4. Use
to confirm the password. A password is not
available as factory default; you can continue without
entering a password.
l/s
.
OK