Function Check; Operation Outside Of Specifications (Out Of Spec.)66 - ABB ProcessMaster FEP611 Operating Instructions Manual

Table of Contents

Advertisement

Error no. / Range
Text on the LCD display
F086.019 / Electronics
Curr.Out 31 / 32 com error.
Defective Board. EMC
disturbance. Call Service.
F084.011 / Electronics
NV data defect.
Data storage irreparable.
Call Service.
F082.014 / Electronics
Incompatible Frontend
Board.
Frontend not fit to
Motherboard. Call Service.
F081.026 / Electronics
MB voltages outside range.
Defective Motherboard HW.
Call Service.
8.2.2

Function check

Error no. / Range
Text on the LCD display
C078.004 / Config.
Flowrate to zero.
Check digital in terminals.
C076.006 / Config.
All totalizer stopp.
Check digital in terminals.
Totalizer reset.
C074.007 / Config.
Reset of one or more
Totalizers.
C072.003 / Config.
Simulation is on Simulated
values.
Switch off Simulation Mode.
An alarm is simulated.
C070.027 / Config.
Switch off alarm simulation.
8.2.3
Operation outside of specifications (Out Of Spec.)
Error no. / Range
Text on the LCD display
S065.044 / Operation
Inhouse temp. alarm.
Reduce ambient
temperature.
S064.041 / Operation
EPD alarm.
Secure pipe is completely
filled.
S062.039 / Operation
Sensor temp. limits alarm.
Change limits or change fluid
temperature.
S052.017 / Operation
Curr.Out 31 / 32 is
saturated.
CO process value out of
range. Adapt Qmax.
S047.016 / Operation
Pulse output is cut off.
Wrong config. Check pulse
out configuration.
66 OI/FEP610/FEH610-EN Rev. B | ProcessMaster FEP610, HygienicMaster FEH610
Cause
Defective Motherboard Hardware.
EMC disturbance.
Data in SensorMemory corrupt.
Wrong Frontend or Mother Board.
Defective Mother Board Hardware.
Cause
The option card Digital Input is configured to
"set flowrate to zero" and this event is
triggered.
The option card Digital Input is configured to
"All Totalizer stopp" and this event is
triggered.
The option card Digital Input is configured to
"ResetTotalizer" and this event is triggered.
The simulation of a process value or an
output is active.
The simulation of an alarm is active.
Cause
Fluid or ambient temperature is out of spec.
Sensor not filled.
The fluid temperature is out of Limits.
The selected current output 31 / 32 process
value is out of measuring range.
The caluclated output pulse or frequency is
above the configurated limit frequency.
Remedy
Call Service.
Call Service.
Call Service.
Replace Mother Board.
Call Service.
Remedy
Check Digital Input terminals and
configuration.
Check Digital Input terminals and
configuration.
Check Digital Input terminals and
configuration.
Switch off simulation mode.
Switch alarm simulation to "Off".
Remedy
Check proces conditions reduce temperature.
Check for empty pipe Make sure sensor is
filled completely.
Check process condition and adjust alarm
limits.
Adapt measuring range.
Check pulse out configuration.