ABB ProcessMaster FEP611 Operating Instructions Manual page 54

Table of Contents

Advertisement

Menu / parameter
Device Setup / ...Sensor / ...Operating Mode
Flow Direction
Flow Indication
Device Setup / ...Transmitter
...Units
Damping
Damping On/Off
Density Fixed Value
...Cut Off
TX Location TAG
TX TAG
Device Reset
Restore Factory Def.
...Feature Settings
...System Zero
Noise Reduction
54 OI/FEP610/FEH610-EN Rev. B | ProcessMaster FEP610, HygienicMaster FEH610
Description
Sets the measuring direction for the sensor.
As delivered, the device measures and counts in both flow directions.
— Forward & Reverse: The device measures in both flow directions.
— Forward only: The device measures only in the forward flow direction.
— Reverse only: The device measures only in the reverse flow direction.
Default setting: Forward & Reverse
Inverts the flow direction displayed.
Default setting: Normal
Selection of submenu "...Units" using
Select the damping.
The value (0.02 ... 60 s) set here relates to 1 Τ (Tau). The value refers to the response time for a step flowrate
change. It affects the instantaneous value in the display and at the current output.
Default setting: 1 second
Switches the damping on or off.
If the flow is measured and indicated in mass flow units, a fixed density must be taken into account for the
calculations. To convert the flow rate to mass flow units, a density value from 0.01 ... 5.0 g/cm
Selection of submenu "...Cut Off" using
Entry of the measuring point tag for the transmitter.
Alphanumeric, max. 20 characters
Entry of the TAG number for the transmitter.
Alphanumeric, max. 20 characters
For service purposes only. Restarts the device without the need for cycling the power.
All user-accessible parameters will be reset to the factory default settings.
Selection of submenu "...Feature Settings" using
Selection of submenu "...System Zero" using
Enables noise reduction filtering technology.
Filter: Off, Filter 15, 30, 60 (15:less filtering, 60: strong filtering)
Filter setting effects 20 mA signal (damping)
Default setting: Off
.
.
.
.