5.5.7

Connection to integral mount design

A
C
Fig. 39: Connection on the device (example), dimensions in mm (inch)
PE = potential equalization
Change from one to two columns
NOTE
If the O-ring gasket is seated incorrectly or damaged,
this may have an adverse effect on the housing
protection class.
Follow the instructions in chapter "Opening and closing the
terminal box" on page 18 to open and close the housing
safely.
Connect compact design: Perform steps A ... C.
In the process, observe the following instructions:
— Lead the cable for the power supply into the terminal box
through the left cable entry.
— Lead the cables for the analog outputs and the digital
outputs into the terminal box through the right cable entry.
— Connect the cables according to the electrical plan.
Connect the cable shields to the designated grounding
clamp in the terminal box.
— Connect the potential equalization (PE) on the ground
terminal to the terminal box.
— Use wire end ferrules when connecting.
B
NOTE
— Observe the power supply limit values in accordance
with the information on the name plate.
— Observe the voltage drop for large cable lengths and
small conductor cross-sections. The voltage at the
terminals of the device may not fall below the minimum
value required in accordance with the information on the
name plate.
The power supply is connected to terminal L (phase),
N (neutral), or 1+, 2-, and PE, as stated on the name plate.
A circuit breaker with a maximum rated current of 16 A must
be installed in the power supply line of the transmitter.
The wire cross-sectional area of the power supply cable and
the circuit breaker used must comply with VDE 0100 and must
be dimensioned in accordance with the current consumption
of the flowmeter measuring system. The cables must comply
with IEC 227 and/or IEC 245.
The circuit breaker should be located near the transmitter and
marked as being associated with the device.
Connect the transmitter and sensor to functional earth.
ProcessMaster FEP610, HygienicMaster FEH610 | OI/FEP610/FEH610-EN Rev. B 27
1+
2-
31 32 41 42 51
10 (0.4)
15 (0.6)
PE
M 20 mm /
NPT 1/2"
100 ... 240 AC
11 ... 30 V DC
52
4 ... 20 mA
DO1 + DO2
G12027