Error no. /
Error text
Range
C078.004 /
Flowrate to zero.
Config.
Check digital in terminals.
C076.006 /
All totalizer stopp.
Config.
Check digital in terminals.
C074.007 /
Totalizer reset.
Config.
Reset of one or more
Totalizers.
C072.003 /
Simulation is on Simulated
Config.
values.
Switch off Simulation Mode.
C070.027 /
An alarm is simulated.
Switch off alarm simulation.
Config.
Inhouse temp. alarm.
S065.044 /
Reduce ambient
Operation
temperature.
S064.041 /
EPD alarm.
Operation
Secure pipe is completely
filled.
S062.039 /
Sensor temp. limits alarm.
Change limits or change fluid
Operation
temperature.
S052.017 /
Curr.Out 31 / 32 is
Operation
saturated.
CO process value out of
range. Adapt Qmax.
S047.016 /
Pulse output is cut off.
Operation
Wrong config. Check pulse
out configuration.
S046.001 /
Mass flowrate exceeds
Operation
limits.
Check flowrate and alarm
limits.
S044.002 /
Volume flowrate exceeds
Operation
limits.
Check flowrate and alarm
limits.
S041.034 /
DC feedback regulation.
Electronics
Check conditions of
application. Call service.
S040.031 /
Coil impedance alarm.
Electronics
Call service.
Current output
Digital output
4 mA (0 % flow)
Current value - no
change.
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
Current value - no
No response
change.
Alarm - as
Alarm if DO is
configured in
configured as
menu "Curr. at
"Logic / Alarm
EPD Alarm".
Signal / EPD".
Current value - no
No response
change.
Alarm - as
Current value - no
configured in
change.
menu "Curr.Out >
20.5mA".
Current value - no
Current value - no
change.
change.
Current value - no
Alarm if DO is
change.
configured as "Qm
Massflow Max" or
"Qm Massflow
Min".
Current value - no
Alarm if DO is
change.
configured as "Qv
Volumeflow Max"
or "Qv Volumeflow
Min".
4 mA (0 % flow)
No response.
Current value - no
No response.
change.
ProcessMaster FEP610, HygienicMaster FEH610 | OI/FEP610/FEH610-EN Rev. B 69
Pulse output
LCD display
0 Hz
0 %
Current value -
Current value -
no change.
no change.
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
No response
Current value - no
change.
0
0 %
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
Maximum possible
Current value - no
pulse rate
change.
Current value - no
Current value - no
change.
change.
Current value - no
Current value - no
change.
change.
0 Hz
0 %
Current value - no
Current value - no
change.
change.
Error maskable?
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".
Menu "...Group
Masking".