Emc Test Results - Danfoss VLT FC 101 Quick Manual

Hvac basic drive
Hide thumbs Also See for VLT FC 101:
Table of Contents

Advertisement

Quick Guide

1.7.5 EMC Test Results

The following test results have been obtained using a system with a Adjustable frequency drive, a shielded control cable, a
control box with potentiometer, as well as a motor shielded cable.
RFI Filter
Conduct emission. Maximum shielded cable length (m)
Type
Industrial environment
EN 55011 Class A2
Without
With
external
external
filter
filter
H4 RFI filter
(Class A1)
0.34–15 hp
[0.25–11 kW]
3 x 200–240
V IP20
0.5–30 hp
[0.37–22 kW]
3 x 380–480
V IP20
H2 RFI filter
(Class A2)
20–60 hp
[15–45 kW]
25
3 x 200–240
V IP20
40–125 hp
[30–90 kW]
25
3 x 380–480
V IP20
1–25 [0.75–
18.5 kW]
25
3 x 380–480
V IP54
30–125 hp
[22–90 kW]
25
3 x 380–480
V IP54
H3 RFI filter
(Class A1/B)
20–60 hp
[15–45 kW]
3 x 200–240
V IP20
40–125 hp
[30–90 kW]
3 x 380–480
V IP20
VLT HVAC Basic Drive Quick Guide
Housing, trades and
light industries
EN 55011 Class A1
EN 55011 Class B
Without
With
Without
external
external
external
filter
filter
filter
25
50
25
50
50
20
50
20
®
MG18A322 - VLT
is a registered Danfoss trademark
Radiated emission
Industrial environment
EN 55011 Class A1
With
Without
With
external
external
external
filter
filter
filter
20
Yes
Yes
20
Yes
Yes
No
No
Yes
No
Yes
Yes
1
Housing, trades and
light industries
EN 55011 Class B
Without
With
external
external
filter
filter
-
-
-
-
-
-
-
1-41