Warnings And Alarms - Danfoss VLT FC 101 Quick Manual

Hvac basic drive
Hide thumbs Also See for VLT FC 101:
Table of Contents

Advertisement

Quick Guide

1.6 Warnings and Alarms

Alarm/
Warning
Fault
Bit
number
Number Fault text
2
16
Live zero error
4
14
Mains ph. loss
7
11
DC overvolt
8
10
DC undervolt
Inverter
9
9
overload
Motor ETR
10
8
over
11
7
Motor th over
13
5
Overcurrent
14
2
Ground Fault
16
12
Short Circuit
17
4
Ctrl.word TO
24
50
Fan Fault
30
19
U phase loss
31
20
V phase loss
32
21
W phase loss
38
17
Internal fault
44
28
Ground Fault
Control
47
23
Voltage Fault
VDD1 Supply
48
25
Low
AMA
Calibration
50
failed
AMA
51
15
Unom,Inom
52
AMA low Inom
AMA big
53
motor
AMA small
54
mot
AMA par.
55
range
AMA user
56
interrupt
57
AMA timeout
VLT HVAC Basic Drive Quick Guide
Trip
Warning Alarm
locked Cause of problem
Signal on terminal 53 or 54 is less than 50% of value set in par.
X
X
6-10, 6-12, 6-20 or 6-22. See also parameter group 6-0X
Missing phase on supply side or too high voltage imbalance. Check
X
X
X
supply voltage. See parameter 14-12
X
X
Intermediate circuit voltage exceeds the limit.
Intermediate circuit voltage drops below the "voltage warning low"
X
X
limit.
X
X
More than 100% load for too long.
Motor is too hot due to more than 100% load for too long. See
X
X
parameter 1-90
The thermistor or the thermistor connection is disconnected. See
X
X
parameter 1-90.
X
X
X
Inverter peak current limit is exceeded.
X
X
Discharge from output phases to ground.
X
X
Short-circuit in the motor or on the motor terminals.
No communication to Adjustable frequency drive. See parameter
X
X
group 8-0X
The fan is not working (Only on 400 V 40–125 hp [30–90 kW]
X
X
units).
X
X
Motor phase U is missing. Check the phase. See parameter 4-58.
X
X
Motor phase V is missing. Check the phase. See parameter 4-58.
X
X
Motor phase W is missing. Check the phase. See parameter 4-58.
X
X
Contact your local Danfoss supplier.
X
X
Discharge from output phases to ground.
X
X
X
24 V DC may be overloaded.
X
X
Control voltage low. Please contact your local Danfoss supplier.
X
Contact your local Danfoss supplier.
The setting of motor voltage, motor current and motor power is
X
presumably wrong. Check the settings.
X
The motor current is too low. Check the settings.
X
The motor is too big for the AMA to be carried out
X
The motor is too small for the AMA to be carried out
The parameter values found from the motor are outside acceptable
X
range.
X
The AMA has been interrupted by the user
Try to start the AMA again a number of times, until the AMA is
carried out. Please note that repeated runs may heat the motor to
a level where the resistances Rs and Rr are increased. In most
X
cases, however, this is not critical.
®
MG18A322 - VLT
is a registered Danfoss trademark
1
1
1-33