Quick Guide
1
1
RFI Filter
Type
1–25 [0.75–
18.5 kW]
3 x 380–480
V IP54
30–125 hp
[22–90 kW]
3 x 380–480
V IP54
Table 1.39
Protection and features
Electronic thermal motor protection against overload.
Temperature monitoring of the heatsink ensures that the Adjustable frequency drive trips in case of overtem-
perature.
The Adjustable frequency drive is protected against short-circuits between motor terminals U, V, W.
If a motor phase is missing, the Adjustable frequency drive trips and issues an alarm.
If a line phase is missing, the Adjustable frequency drive trips or issues a warning (depending on the load).
Monitoring of the intermediate circuit voltage ensures that the Adjustable frequency drive trips if the intermediate
circuit voltage is too low or too high.
The Adjustable frequency drive is protected against ground faults on motor terminals U, V, W.
Line power supply (L1, L2, L3)
Supply voltage
Supply voltage
Supply voltage
Supply frequency
Max. imbalance temporary between line phases
True Power Factor (λ)
Displacement Power Factor (cosφ) near unity
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H1-H5, I2, I3
Switching on the input supply L1, L2, L3 (power-ups) enclosure frame H6-H8, I6-I8
Environment according to EN 60664-1
The unit is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical Amperes, 240/480 V
maximum.
Motor output (U, V, W)
Output voltage
Output frequency
Switching on output
Ramp times
Cable lengths and cross-sections
Max. motor cable length, shielded/armored (EMC-compliant installation)
Max. motor cable length, unshielded/unarmored
Max. cross-section to motor, line power*
Cross-section DC terminals for filter feedback on enclosure frame H1-H3, I2, I3
Cross-section DC terminals for filter feedback on enclosure frame H4-H5
Maximum cross-section to control terminals, rigid wire
Maximum cross-section to control terminals, flexible cable
1-42
VLT HVAC Basic Drive Quick Guide
Conduct emission. Maximum shielded cable length (m)
25
50
MG18A322 - VLT
10
10
overvoltage category III/pollution degree 2
®
is a registered Danfoss trademark
Radiated emission
Yes
Yes
-
200–240 V ±10%
380–480 V ±10%
525–600 V ±10%
3.0% of rated supply voltage
≥ 0.9 nominal at rated load
Max. twice/min.
Max. once/min.
0–100% of supply voltage
0–200 Hz (VVC
plus
), 0–400 Hz (u/f)
Unlimited
0.05–3,600 sec.
See 1.7.5 EMC Test Results
164 ft [50 m]
2
4 mm
16 mm
2
2.5 mm
/14 AWG)
2.5 mm
2
/14 AWG)
50/60 Hz
(> 0.98)
/11 AWG
2
/6 AWG