Variable name
_EIP_TagAdrErr
Meaning
Tag Name Resolution Error
Function
Indicates that the tag resolution for CIP communications 1 failed (i.e., the address could not be identified from the
tag name).
TRUE: Tag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
The size of the network variable is different from the tag settings.
The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the Communication Control Unit.
There is no network variable in the Communication Control Unit that corresponds to the tag setting.
FALSE: Other than the above.
Data type
BOOL
R/W access
R
Variable name
_EIP1_TagAdrErr
Meaning
CIP Communications1 Tag Name Resolution
Error
Function
Indicates that the tag resolution for CIP communications 1 failed (i.e., the address could not be identified from the
tag name).
TRUE: Tag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
The size of the network variable is different from the tag settings.
The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the Communication Control Unit.
There is no network variable in the Communication Control Unit that corresponds to the tag setting.
FALSE: Other than the above.
Data type
BOOL
R/W access
R
Variable name
_EIP2_TagAdrErr
Meaning
CIP Communications2 Tag Name Resolution
Error
Function
Indicates that the tag resolution for CIP communications 2 failed (i.e., the address could not be identified from the
tag name).
TRUE: Tag resolution failed (i.e., the address could not be identified from the tag name). The following causes are
possible.
The size of the network variable is different from the tag settings.
The I/O direction that is set in the tag data link settings does not agree with the I/O direction of the variable in
the Communication Control Unit.
There is no network variable in the Communication Control Unit that corresponds to the tag setting.
FALSE: Other than the above.
Data type
BOOL
R/W access
R
NX-series Communication Control Unit Built-in Function User's Manual (Z396)
Retained
Not retained.
Retained
Not retained.
Retained
Not retained.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.
Global/local
Global
Range of values
TRUE or FALSE
Network Publish
Published.