Reconnect A Unit To A Parallel System - GE SG SERIES 10 Operating Manual

10, 20, 30 and 40 kva
Table of Contents

Advertisement

g

7.3.5 Reconnect a Unit to a parallel system

1. Connect the Utility supply on the separated Unit.
Press mute, to reset alarm and buzzer.
First operated unit
2. Close Q1 (Pos. I) on the separated Unit.
Rectifier starts automatically.
First operated unit
3. Connect the Battery, in case of External Battery, to the UPS on the separated
Unit by closing the external Battery Switch or Fuses.
4. Press "inverter on" ( I ) key on the separated Unit.
After Soft-start of the Inverter, the Inverter connects automatically to the other Units
of the parallel system.
The LCD must display on the main screen the status "LOAD ON INVERTER".
First operated unit
OPM_SGS_USM_10K_40K_0US_V010.doc
All other units of the system
All other units of the system
All other units of the system
End of procedure
Operating Manual SG Series 10, 20, 30 & 40 kVA
59/88
GE

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents