Chapter 18

18.3 Checking Error Information

18.3.1

Checking trip information

Q
• The inverter generated an error and tripped. You
want to see the information of the moment the error
occurred.
A
• Up to 10 trips in the past is displayed as the trip
history.
• The latest trip history is displayed on the trip
monitor 1.
• The following data items are displayed on the
monitor:
1) Error factor for trip
2) Output frequency (Hz) at trip
3) Output current (A) at trip
4) Main circuit DC voltage (V) at trip
5) Operation state at trip
6) Cumulative inverter operating time (h) before trip
7) Cumulative inverter power-on time (h) before trip
Parameter
Item
Trip monitor 1 to 10
Trip count monitor
"Detailed monitor" for checking the history
• You can look through the history
with the arrow keys.
Trip history
Total count 20 times
6. E001 16/05/10 19:22
7. E001 16/04/21 20:59
8. E007 16/03/30 23:55
9. E001 15/12/25 01:34
10. E005 15/12/24 22:10
Parameter
See above data
Detailed monitor
Detailed monitor
0 - 65535 (Counts)
STOP
Trip history
Total count 20 times
1. E007 16/07/15 10:10
2. E001 16/07/15 08:55
3. E001 16/07/15 08:52
4. E009 16/07/12 10:10
5. E012 16/07/10 22:52
Menu
oFW
Trip history details (No.10)
Motor overload error
E005 15/12/24
Output frequency : 0.50Hz
Output current
DC voltage
Status 1
Tips/FAQ/Troubleshooting
!
• The information of the moment of error occurrence
may not be fetched properly if the inverter is
forcibly turned OFF by its hardware.
• Values of respective data items may be reset to 0
when an error occurred and the inverter entered
the trip condition.
• For a ground fault or a momentary overcurrent
event, the current may be recorded in a value lower
than the actual value.
• The trip monitor and the trip count monitor can be
cleared by initialization of the trip history.
Display of occurring trip
TRIP
NRDY
Occurring trip
Motor overload error
E005 15/12/24
Output frequency : 0.50Hz
Output current
DC voltage
Status 1
Back
oFW
Data
On the parameter monitor, you can view
data items 1) to 7) in sequence by
items.
UP/DOWN keys.
Trip count data is stored in the inverter.
H06
M1
Details
46.49Hz
22:10
: 49.71A
: 274.1Vdc
: Run
18-3
H07
M1
22:10
: 49.71A
: 274.1Vdc
: Run
----
46.49Hz
Description
Trip history details (No.10)
Motor overload error
Status 3
: Speed control
Status 4
: Overload limit
Status 5
: ----
RUN time
: 20256 hr
ON time
: 27248 hr