13.19 Checking the Operation and
Frequency Command
Destinations
Q
• Want to check that the operation command
destinations do not disagree with the contents you
have set.
• Want to check that the frequency command
destinations do not disagree with the contents you
have set.
A
• You can check the operation command destinations
and the frequency command destinations that are
currently enabled.
Parameter
Item
Main speed command
destination monitor
Auxiliary speed
command destination
monitor
Operation command
destination monitor
Parameter
Data
01~07,
[dC-07]
09~34
[dC-08]
00~34
[dC-10]
00~06
!
• Command destinations vary according to the state
of terminal functions as well as to the settings.
Commands not input from the currently enabled
command destinations will be ignored.
00 (disabled), 01 (Ai1), 02 (Ai2), 03 (Ai3),
07 (Multistage speed 0[Ab110]/[Ab210]),
08 (auxiliary speed[AA104]/[AA204]),
09 (Multistage speed 1[Ab-11]),
10 (Multistage speed 2[Ab-12]),
11 (Multistage speed 3[Ab-13]),
12 (Multistage speed 4[Ab-14]),
13 (Multistage speed 5[Ab-15]),
14 (Multistage speed 6[Ab-16]),
15 (Multistage speed 7[Ab-17]),
16 (Multistage speed 8[Ab-18]),
17 (Multistage speed 9[Ab-19]),
18 (Multistage speed 10[Ab-20]),
19 (Multistage speed 11[Ab-21]),
20 (Multistage speed 12[Ab-22]),
21 (Multistage speed 13[Ab-23]),
22 (Multistage speed 14[Ab-24]),
23 (Multistage speed 15[Ab-25]), 24 (JG[AG-20]),
25 (RS485), 29 (Pulse array (inverter)), 31 (EzSQ),
32 (PID), 34 (AHD retention speed)
00 ([FW]/[RV] terminal)/01 (3 wire)/
02 (RUN key on operator keypad)/03 (RS485 setting)/
04 (Option 1)/05 (Option 2)/06 (Option 3)