Chapter 7
7.5 Connect Wire to the Main Circuit
Terminal Block
7.5.1
Configuration of Main Circuit Terminal
Block
Earth-leakage
breaker
ELB
3-phase
AC power
supply
200 V class:
J51 connector
200-240 VAC
400V class:
380-500 VAC
Control circuit
power supply
Selection of EMC filter
The EMC filter is disabled:
Model P1-*****-*FF and P1-*****-*FUF
The EMC filter is enabled:
Model P1-*****-*FEF and P1-*****-*FCF
7.5.2
Description of Main Circuit Terminal
Block
Terminal symbol
R,S,T
Input terminal for
(L1,L2,L3)
main power supply
U,V,W
Inverter output
(T1,T2,T3)
terminal
PD,P
DC reactor
(+1,+)
connection terminal
P,RB
Connection terminal
(+,RB)
for external braking
resistor
P,N
Connection terminal
(+,-)
for regenerative
braking unit
Inverter earth
terminal
Magnetic
contactor
MC
R/L1
S/L2
T/L3
R0
T0
(factory default state)
Terminal name
Connect to the AC power supply. Do not connect these terminals to the
AC power supply when using the harmonic suppression unit HS900A
series.
Connect to the 3-phase motor.
Remove the short bar between PD and P terminals, and connect the
optional reactor DCL for improving power factor.
Connect the optional external braking resistor. For models equipped with
the braking resistor circuit, see "Chapter 20 Specifications". Models not
equipped with the braking resistor circuit does not have the RB terminal.
Connect the optional regenerative braking unit BRD, regenerative
converter RC700, and harmonic suppression unit HS900A.
The earth terminal for the Inverter case. Please connect this terminal to
the ground.
Conduct class-D ground work for 200V class, and class-C ground work
for 400V class.
Wire Connection and Optional Devices
* The RB terminal is mounted only on models
equipped with the drive circuit for braking
resistor.
Internal EMC filter
Short bar or terminal
N
Short bar
Enable
Main circuit
terminal area
Short circuit between P and PD
When shipped from the factory, P and PD
are short-circuited. If P and PD are not
connected, power is not supplied to the
main circuit, which disables operation.
Description
7-6
Short bar
RB
PD
P
3-phase AC motor
U/T1
V/T2
W/T3
D-class grounding
(200V class)
C-class grounding
(400V class)
(factory default state)
M
3~