Chapter 12
12.19.13
Outputting a warning based on the
number of operating hours
• I want to know when the number of operating
hours reaches a certain period of time.
• I want to output with a signal the number of
operating hours of the system in which the inverter
has been incorporated.
• Assign the output terminal function 024 [RNT]
RUN time over signal to one of [CC-01] to [CC-07]
that corresponds to the output terminal and output
the signal.
• Specify the RUN time/power-on time level [CE-36].
• The RUN time over signal [RNT] will be output
when the cumulative total of inverter operating
hours exceeds the time specified with the RUN
time/power-on time level [CE-36].
Parameter
Item
Output terminal function
selection 11-15
Relay output terminal
function selection 16A-16C
Relay output terminal
function selection
AL1-AL0/AL2-AL0
RUN time/power-on time
level
Cumulative operating hours
monitor during RUN
Parameter
[CC-01]~[CC-05]
[CC-06]
[CC-07]
[CE-36]
0~100000[hour]
[dC-22]
0~65535[hour]
12-19-15
• When specifying the time level as a guideline for
replacement, use a number with an adequate
margin.
• Setting example
First time:
When you want to generate a warning after an
operation of (250 days
10,000 hours, set [CE-36] to 10,000.
Second time onward:
When you want to generate a warning after an
operation of (250 days
10,000 hours, set [CE-36] to [dC-22] + 10,000.
Data
The
RUN time over signal [RNT]
OFF: Less than or equal to the RUN time
024
level
ON: More than the RUN time level
This function does not work when this level
has been set to 0. Specify 1 to 100,000
hours.
The number of hours when the inverter
outputs is stored for monitoring.
Inverter Function
8 hours
5 years =)
8 hours
5 years =)
Description
is output.