Chapter 12
Forward/Reverse Drive Stop Function (FOT/ROT)
• Function to prevent the operation range from being
deviated using the signal from the control range limit
switch.
• The torque limit is restricted to 10% on the forward
rotation side when the 082[FOT] terminal is input and on
the reverse rotation side when the 083[ROT] terminal is
input. This is applicable as the limit switch at the edge of
the machine.
Position Range Designation Function
• Specify the position control range at the [AE-52] position
range designation (forward rotation side) /[AE-54]
position range designation (reverse rotation side).
• When the current position counter exceeds this setting,
there is a trip with the position control range error (E104)
and the inverter becomes the free-running status.
Position Control Related Parameters
Function
Item
Control Method
Vector control mode
selection
Multistage position
command 0
Multistage position
command 1
Multistage position
command 2
Multistage position
command 3
Multistage position
command 4
Multistage position
command 5
Multistage position
command 6
Multistage position
command 7
Multistage position
command 8
Multistage position
command 9
Multistage position
command 10
Multistage position
command 11
Multistage position
command 12
Multistage position
command 13
Multistage position
command 14
Multistage position
command 15
Position range
designation (forward
rotation side)
Position range
designation
(reverse rotation side)
Position command
monitor
Data/Data Range
Code
[AA121]
[AA123]
[AE-20]
[AE-22]
[AE-24]
[AE-26]
[AE-28]
[AE-30]
[AE-32]
[AE-34]
[AE-36]
[AE-38]
[AE-40]
[AE-42]
[AE-44]
[AE-46]
[AE-48]
[AE-50]
Condition 1: 0 to +268435455
[AE-52]
Condition 2: 0 to +1073741823
Condition 1: -268435455 to 0
[AE-54]
Condition 2: -1073741823 to 0
Condition 1: -268435455 to +268435455
[FA-20]
Condition 2: -1073741823 to +1073741823
Position Memory at Power-Off
• By setting the [AE-61] current position memory at
power-off to 01, the current position data at
power-off can be stored.
• Use this for the application where the shaft of the
motor is locked at power-off.
!
• For the machine of which the shaft idles at
power-off, there is likely to be a gap between the
stored position and the current position when the
power is turned on again.
Position Data Preset
• When the 085[PSET] terminal is turned on, the
current position counter (can be monitored with
[dA-20]) is overwritten with the value set to the
[AE-62] preset position data.
• Available for restarting in the middle of the
positioning process, etc. (Data is overwritten at the
ON edge of the [PSET] terminal.)
10
02
03
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
[AE-54]~[AE-52]
12-17-30
Inverter Functions
Description
Vector control with sensor
Absolute position control
High resolution absolute position control
Set the position command for the multistage
speed command to each.
Condition 1: Except for the condition 2
Condition 2: [AA121] = 10, [AA123] = 03
Condition 1: Except for the condition 2
Condition 2: [AA121] = 10, [AA123] = 03
Condition 1: Except for the condition 2
Condition 2: [AA121] = 10, [AA123] = 03