Chapter 12
12.25.6
Outputting data with voltage/current
• As inverter information, I want to output
information externally with a voltage.
• As inverter information, I want to output
information externally with a current.
• With Analog output terminals Ao1 and Ao2, you
can select voltage output or current output by
operating Switches SW3 and SW4 on the
substrate.
Parameters
Item
[Ao1] terminal output
selection
[Ao2] terminal output
selection
Analog monitor
adjustment mode
selection
[Ao1] output filter
time constant
[Ao1] output data
type selection
[Ao1] bias
adjustment
(Common to
voltage/current)
[Ao1] gain
adjustment
(Common to
voltage/current)
[Ao1] output level in
the adjustment mode
[Ao2] output filter
time constant
[Ao2] output data
type selection
[Ao2] bias
adjustment
(Common to
voltage/current)
[Ao2] gain
adjustment
(Common to
voltage/current)
[Ao2] output level in
the adjustment mode
Parameter
Parameter number for
[Cd-04]
"12.25.4 Selecting data to be
[Cd-05]
[Cd-10]
1~500[ms]
[Cd-21]
[Cd-22]
-100.0~100.0[%]
[Cd-23]
-1000.0~1000.0[%]
[Cd-24]
-100.0~100.0[%]
[Cd-25]
1~500[ms]
[Cd-31]
[Cd-32]
-100.0~100.0[%]
[Cd-33]
-1000.0~1000.0[%]
[Cd-34]
-100.0~100.0[%]
[Cd-35]
12-25-14
• For outputs of [Ao1] and [Ao2], voltage output has
an initial value in a range from 0 to 10 V, and
current output has an initial value in a range from 4
to 20 mA.
• Operate the switches on the substrate while the
inverter power supply is turned off.
• When [Cd-10]=01 is set, [FM], [Ao1], and [Ao2]
respectively perform outputs in accordance with
values of [Cd-15], [Cd-25], and [Cd-35].
Data
Sets a parameter number.
output"
00
Invalid.
Valid. Outputs to terminals output
01
levels in the adjustment mode.
Filters and outputs the selected
data.
00
Outputs the absolute value of data.
01
Outputs data with a symbol as is.
Biases data to adjust Point 0 of
data.
Apply a gain to data to adjust an
inclination in data.
Sets output in the adjustment
mode. It selects the maximum
output (at 100.0%), the minimum
output (at 0.0%) ([Cd-22]=00), or
the minimum output (at -100.0%)
([Cd-22]=01).
Filters and outputs the selected
data.
00
Outputs the absolute value of data.
01
Outputs data with a symbol as is.
Biases data to adjust Point 0 of
data.
Apply a gain to data to adjust an
inclination in data.
Sets output in the adjustment
mode. It selects the maximum
output (at 100.0%), the minimum
output (at 0.0%) ([Cd-32]=00), or
the minimum output (at -100.0%)
([Cd-32]=01).
About the inverter function