Appendix 1
Code
First low current signal output mode
CE101
selection
CE102
First low current detection level 1
CE103
First low current detection level 2
First overload prewarning signal
CE105
output mode selection
CE106
First overload prewarning level 1
CE107
First overload prewarning level 2
CE-10
Acceleration reaching frequency 1
CE-11
Deceleration reaching frequency 1
CE-12
Acceleration reaching frequency 2
CE-13
Deceleration reaching frequency 2
First over torque level
CE120
(normal powered)
First over torque level
CE121
(reverse regenerative)
First over torque level
CE122
(reverse powered)
First over torque level
CE123
(normal regenerative)
Electronic thermal warning level
CE-30
(MTR)
Electronic thermal warning level
CE-31
(CTL)
CE-33
0-Hz detection value level
CE-34
Cooling fin heating prewarning level
CE-36
RUN time/power-on time level
Name
00 (During acceleration/deceleration,
at constant speed)/
01 (Only at constant speed)
(0.00 to 2.00)
× Inverter rated current
(0.00 to 2.00)
× Inverter rated current
00 (During acceleration/deceleration,
at constant speed)/
01 (Only at constant speed)
(0.00 to 2.00)
× Inverter rated current
(0.00 to 2.00)
× Inverter rated current
0.00~590.00 (Hz)
0.00~590.00 (Hz)
0.00~590.00 (Hz)
0.00~590.00 (Hz)
0.0~500.0 (%)
0.0~500.0 (%)
0.0~500.0 (%)
0.0~500.0 (%)
0.00~100.00 (%)
0.00~100.00 (%)
0.00~100.00 (%)
0~200 (°C)
0~100000 (hr)
Appendix 1-42
Data range
Initial value
× Inverter
rated current
× Inverter
rated current
× Inverter
rated current
× Inverter
rated current
List of Parameters
Note
01
1.00
1.00
01
1.00
1.00
0.00
0.00
0.00
0.00
100.0
100.0
12-11-9
100.0
100.0
80.00
80.00
0.50
120
0