Chapter 4
4.1.28 Trip monitoring 1 to 6
When the trip monitoring function (d081 to d086) is selected, the inverter
displays the trip history data. The last six protective trips the inverter made can
be displayed.
Select the trip monitoring 1 (d081) to display the data on the most recent trip.
(Display contents)
1) Factor of tripping (one of E01 to E79) (*1)
2) Output frequency at tripping (Hz)
3) Output current at tripping (A) (*2)
4) Main circuit DC voltage at tripping (V) (*3)
5) Cumulative inverter-running time until tripping (h)
6) Cumulative inverter power-on time until tripping (h)
*1 See Section 5.1.1, "Protective functions."
*2 When the inverter status is in stop mode as a trip history, monitored value can be zero.
*3 When grounding fault is detected at power on, monitored value can be zero.
(Display by trip monitoring)
1) Factor of
tripping
(*2)
FUNC
*2 If the inverter has not tripped before, the inverter displays
4.1.29 Programming error monitoring
If an attempt is made to set the data conflicting with other data on the inverter, the
inverter displays a warning.
The PRG (program) lamp lights up while the warning is displayed (until the data is rewritten forcibly or corrected).
For details on the programming error monitoring function, see Section 5.2. Warning Codes
4.1.30 DC voltage monitoring
When the DC voltage monitoring is selected, the inverter displays the DC voltage (across
terminals P and N) of the inverter.
While the inverter is operating, the monitored value changes as the actual DC voltage of the inverter changes.
(Display)
0.0 to 999.9 in steps of 0.1 V
4.1.31 BRD load factor monitoring
When the BRD load factor monitoring function (d103) is selected, the inverter displays the
BRD load factor. If the BRD load factor exceeds the value set as the dynamic braking usage
ratio (b090), the inverter will trip because of the braking resistor overload protection (error
code "E06").
(Display)
0.0 to 100.0 in steps of 0.1%
4.1.32 Electronic thermal overload monitoring
When the electronic thermal overload monitoring function (d104) is selected, the inverter
displays the electronic thermal overload. If the electronic thermal overload exceeds 100%,
the inverter will trip because of the overload protection (error code "E05").
(Display)
0.0 to 100.0 in steps of 0.1%
2) Frequency at
3) Current at
tripping
tripping
Explanation of Functions
4) Main circuit DC
5) Cumulative
voltage at tripping
FUNC
.
4-6
Related code
d081: Trip monitoring 1
d082: Trip monitoring 2
d083: Trip monitoring 3
d084: Trip monitoring 4
d085: Trip monitoring 5
d086: Trip monitoring 6
6) Cumulative
running time
power-on time
Related code
d090: Programming error monitoring
Related code
d102: DC voltage monitoring
Related code
d103: BRD load factor monitoring
b090: Dynamic braking usage ratio
Related code
d104: Electronic thermal overload
monitoring