Chapter 20
20.2.2
400V Class Specifications
Model symbol
P1-*****-H
ND capacity standard notation
P1-***H
Applicable motor (4-pole)
capacity (kW)
Rated output
current (A)
Overload current
rating
Output
Rated output voltage
400V
Rated
capacity
(kVA)
500V
Rated input current
(A) *1)
Input
Rated input AC voltage *2)
Power supply
equipment capacity
(kVA) *3)
Carrier frequency range *4)
Motor start torque*5)
Regenerative braking
Braking
Minimum resistance that
can be connected (Ω)
H (height) (mm)
Dimension
W (width) (mm)
*7)
D (depth) (mm)
Protective construction
Approximate mass (kg)
*1) The values shown are ratings when carrier frequency is at 2kHz. Please
use the inverter in accordance with "20.4 Current Derating Table".
*2) The rated input currents shown in the table are the values when the rated
current is output. The values vary depending on impedance on the
power supply (wiring, breaker, input reactor option, etc.)
*3) The following shows response to the Low Voltage Directive.
- Pollution degree 2
- Overvoltage category 3 (when input voltage is between 380 and 460
VAC)
- Overvoltage category 2 (when input voltage is higher than 460 VAC)
*4) The power supply equipment capacities shown in the table are the
values when 440V rated current is output. The values vary depending on
impedance on the power supply (wiring, breaker, input reactor option,
etc.)
*5) The setting of rated values for carrier frequencies [bb101]/[bb201] are
internally limited in accordance with the description. Also, it is
recommended to set values equivalent to or above (maximum output
frequency for driving ×10) Hz for the setting of carrier frequencies
[bb101]/[bb201]. Also, in the case of induction motor (IM) control, for
items other than those subject to V/f control, it is recommended to set
carrier frequency at 2kHz or more. In the case of synchronous motor
(SM)/permanent magnet motor (PMM) control, it is recommended to set
carrier frequency at 8kHz or more.
00041 00054 00083 00126 00175 00250 00310 00400 00470 00620 00770 00930 01160 01470 01760 02130 02520 03160
007
015
022
037
055
1.5
2.2
3.7
5.5
7.5
VLD
LD
1.5
2.2
3.7
5.5
7.5
ND
0.75
1.5
2.2
3.7
5.5
4.1
5.4
8.3
12.6 17.5 25.0 31.0 40.0 47.0 62.0 77.0 93.0
VLD
3.1
4.8
6.7
11.1 16.0 22.0 29.0 37.0 43.0 57.0 70.0 85.0
LD
2.5
4.0
5.5
9.2
14.8 19.0 25.0 32.0 39.0 48.0 61.0 75.0 91.0
ND
VLD
LD
ND
2.8
3.7
5.8
8.7
12.1 17.3 21.5 27.7 32.6 43.0 53.3 64.4 80.4 101.8 121.9 147.6 174.6 218.9
VLD
2.1
3.3
4.6
7.7
11.1 15.2 20.1 25.6 29.8 39.5 48.5 58.9 72.7 93.5 110.9 135.1 159.3 200.9
LD
1.7
2.8
3.8
6.4
10.3 13.2 17.3 22.2 27.0 33.3 42.3 52.0 63.0 77.6 103.9 124.7 150.3 180.1
ND
3.6
4.7
7.2
10.9 15.2 21.7 26.8 34.6 40.7 53.7 66.7 80.5 100.5 127.3 152.4 184.5 218.2 273.7
VLD
2.7
4.2
5.8
9.6
13.9 19.1 25.1 32.0 37.2 49.4 60.6 73.6 90.9 116.9 138.6 168.9 199.2 251.1
LD
2.2
3.5
4.8
8.0
12.8 16.5 21.7 27.7 33.8 41.6 52.8 65.0 78.8 97.0 129.9 155.9 187.9 225.2
ND
VLD
4.9
6.4
9.9
15.0 20.8 29.8 36.9 47.6 56.0 73.8 91.7 110.7 138.1 175.0 209.5 253.6 300.0 376.2
LD
3.7
5.7
8.0
13.2 19.0 26.2 34.5 44.0 51.2 67.9 83.3 101.2 125.0 160.7 190.5 232.1 273.8 345.2
ND
3.0
4.8
6.5
11.0 17.6 22.6 29.8 38.1 46.4 57.1 72.6 89.3 108.3 133.3 178.6 214.3 258.3 309.5
Control power supply: Power supply single phase 380-500V (allowable variation range 323-550V),
50Hz (allowable variation range: 47.5-52.5Hz)/60Hz (allowable variation range: 57-63Hz)
Main circuit power supply: 3-phase (3-wire) 380-500V (allowable variation range) 323-550V,
50Hz (allowable variation range: 47.5-52.5Hz)/60Hz (allowable variation range: 57-63Hz)
3.7
4.9
7.5
11.4 15.9 22.7 28.1 36.3 42.6 56.3 69.9 84.4 105.2 133.4 159.7 193.2 228.6 286.7
VLD
2.8
4.4
6.1
10.1 14.5 20.0 26.3 33.6 39.0 51.7 63.5 77.1 95.3 122.5 145.2 176.9 208.7 263.1
LD
2.3
3.6
5.0
8.3
13.4 17.2 22.7 29.0 35.4 43.5 55.3 68.0 82.6 101.6 136.1 163.3 196.9 235.9
ND
VLD
LD
ND
Equipped with braking resistance circuit
(with a discharging resistor separately installed)
100
100
100
70
255
255
255
255
260
150
150
150
150
210
140
140
140
140
170
3
3
3
3
* The models in 400V class are shown as P1-*****-HFF or
P1-*****-HFEF, P1-*****-HFUF, or P1-*****-HFCF.***** filled with
numbers described in "Model symbol".
075
110
150
185
220
11
15
18.5
22
30
11
15
18.5
22
30
7.5
11
15
18.5
22
110% 60sec / 120% 3sec
120% 60sec / 150% 3sec
150% 60sec / 200% 3sec
3-phase (3-wire) 380-500V (depending on receiving voltage)
0.5~10.0kHz
0.5~12.0kHz
0.5~16.0kHz
200%/0.3Hz
70
35
35
24
24
20
260
260
390
390
390
210
210
245
245
245
170
170
190
190
190
IP20 / UL open type
7
7
7
16
16
16
*6) Values when sensorless vector control is applied at ND rating on a
Hitachi's standard motor. Torque characteristics may be different
depending on the control method or motor for use.
*7) The dimensions do not include buttons on the operator keypad.
When optional items are connected, the required dimensions will
increase. Check the instruction manuals of each optional item for details.
*8) Usually a regenerative braking unit needs to e separately installed,
however, in response to your order, we can install the braking circuit
internally and attach a discharging resistor, thereby eliminating the need
for the regenerative braking unit. Please contact the sales officer of our
company shown in the back cover.
20-3
Specifications
300
370
450
550
750
900 1100 1320
37
45
55
75
90
110
37
45
55
75
90
110
30
37
45
55
75
90
116
147
176
213
105
135
160
195
112
150
180
0.5~8.0kHz
0.5~8.0kHz
0.5~10.0kHz
180%/0.3Hz
*6)
Regenerative braking unit
separately installed
15
10
10
15
-
550
550
550
700
700
540
390
390
390
390
390
300
250
250
250
270
270
195
22
30
30
30
55
55
132
160
132
160
110
132
252
316
230
290
217
260
-
-
-
740
740
480
480
270
270
70
70