Chapter 14
14.5.2
EzCOM Settings
• Set a station number for [CF-02] to each inverter of
the EzCOM network, avoiding overlapping a station
number. While doing so, make sure to assign a
station number 01. The inverter with the station
number 01 will be the "controlling inverter".
• Set the communication selection of controlling
inverter to EzCOM communication's "controlling
inverter" [CF-09]=02. Set the communication
selection
of
other
communication [CF-09]=01.
Item
Communication station number
selection *1)
Communication error operation
selection
Communication timeout time
Communication waiting time
Communication selection
EzCOM master start station
number *2)
EzCOM master end station
number *2)
EzCOM start selection
Input terminal 1 to 9, A or B
selection
Set-up destinations
ALL: Set to all inverters used for EzCOM.
A:
Set to only an inverter for controlling (station
number 01).
B:
Set to inverters other than an inverter for
controlling (station number 01).
inverters
to
EzCOM
Parameter
Data
[CF-02]
1~247
[CF-06]
00
01
02
03
04
[CF-07]
0.00
0.01~100.00
[CF-08]
0.~1000.
[CF-09]
00
01
02
[CF-20]
01~08
[CF-21]
01~08
[CF-22]
00
01
[CA-01]~[CA-11]
098
14-22
RS485 Communication
• Set the EzCOM communication start method
[CF-22] to the controlling inverter. If you selected
the input terminal start [CF-22]=00, assign 098
[485:EzCOM start] to any of input terminals 1 - 9, A
or B.
• To a master inverter, set the number of transmitting
data,
the
station
destination, register of transmission destination,
and register of transmission source that are
required for the master inverter to write the data
(see the following table).
Set-up
Destination
ALL
Station number setting
ALL
Trip
ALL
Trips after decelerating and stopping
ALL
Ignore
ALL
Free-run
ALL
Deceleration stop
ALL
Communication timeout disabled
ALL
Unit [s]
ALL
Unit [ms]
Modbus-RTU communication
B
EzCOM communication
A
EzCOM communication <controlling
inverter>
A
Setting required for controlling inverter only.
A
Setting required for controlling inverter only.
A
Start-up by input terminal
A
Always communication
A
[ECOM]: Starting up of EzCOM
*1) When you provide multiple master inverters, set
consecutive station numbers (01, 02, 03, ...) to
them. If the numbers are not consecutive, the
inverters cannot perform communication.
*2) Note that the relationship between the master
start/end station number settings must be
[CF-20] ≤ [CF-21].
number
of
transmission
Description