Display And Recording Of Relays - wtw TresCon UNO A111 Operating Manual

Table of Contents

Advertisement

TresCon UNO
Display of the
relays in the measured
value display
Recording
ba43134e08
05/2017

5.3.9 Display and recording of relays

The allocated relays appear on the display as additional information to
each measured value.
Allocated
relays
Fig. 5-16 Display: Display of the relays
Below the measured value, all the linked relays K1...n are displayed. A
relay that is being active is displayed in reverse video.
If the Messages record mode is activated, a record is output (example
Fig. 5-17).
Relay parameters 1
-----------------------------------------
PO4-P outlet activation
Function: Pulse-width controller
Cmin: 0.50 mg/l PO4-P
Cmax: 1.50 mg/l PO4-P
tmin: 5
s
tmax: 100
s
Action: Normally open
-----------------------------------------
TresCon>
Fig. 5-17 Example of a Relay parameters record
Operation
5 - 49

Advertisement

Table of Contents
loading

Table of Contents