Configuration 13 - Allen-Bradley Guardmaster GuardLink User Manual

Safety system
Table of Contents

Advertisement

Configuration 4
Figure 72 - One Safety Input, Middle SWS, Monitored Manual Reset Assigned to Safety Outputs
Schematic
+24V DC
Test Out
A1
S11
S21
GSR
DG
CI/SI/DI/DIS
440R-DG2R2T
A2
L12 L11
S32
S42
IN X
24V DC Com
In Configuration 4, only safety Input 1 is in use. It can either be configured for
GuardLink or OSSD with autodetect of EMSS devices. Input devices are not
shown in the drawing.
The input IN X (terminal X1) is configured for SWS In. This input is ANDed
with IN 1.
The output OUT X (terminal X2) is configured for SWS Out and can drive
any other SWS compatible device. In this example, the SWS out is driving an
EM safety relay. OUT X is switched off immediately when demanded by the
safety functions. The relay outputs 14/24 can be configured for a time delay to
switch off after the delay time.
The relay configuration is considered a middle SWS as it requires an SWS
input and provides an SWS output.
The Reset mode is configured for manual monitored reset and is assigned to
the safety outputs. The outputs are enabled when all inputs of the safety
function are ACTIVE, the feedback signal is present, and a valid reset
operation has been performed.
Input 1
Reset
A1
S12
S22
A1
13 23
X4
TIME
EM
440R-EM4R2
X3
A2
L12
X1
X2
A2
14
24
OUT X
SWS
K1
K2
Table 32 - Configuration 4
Indicator
OUT
IN 1
IN 2
OUT X
IN X
Reset
FB
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
K1
X32
13 23 33 43
K2
K3
L11
14 24
34
44
K4
Feedback
K3
K4
Function
Configuration ID: 0x7A
Safety Functions
IN1
Input Type
GuardLink
Input Type
Not used
Output Type
SWS
Input Mode
SWS Enabled
Reset Type
Monitored Manual
Reset Assignment
SOF
Configuration Examples
Appendix B
Logic
IN 1
IN X
SMF Level
&
LOGIC Level
R
SOF Level
FB
OUT X
OUT 14/24
Configuration ID: 0x78
IN1
OSSD/EMSS
Not used
SWS
SWS Enabled
Monitored Manual
SOF
99