Appendix B
Configuration Examples
Configuration 19
Figure 87 - First SWS Device, One Safety Input, Monitored Manual Reset Assigned to Safety Outputs
Schematic
+24V DC
Test Out
Input 1
S11
S21
S12
In
+24
+24
Machine
O3
Control
O2
System
DG
O1
440R-DG2R2T
O0
Com
S32
S42
X1
OUT X
24V DC Com
114
In Configuration 19, only safety Input 1 is in use. It can either be configured
for GuardLink or OSSD with autodetect of EMSS devices. Input devices are
not shown in the drawing.
The input IN X (terminal X1) is disabled. The output type for OUT X
(terminal X2) is configured for OSSD and can be used as a status output or to
drive another control device.
The reset mode is configured for manual monitored reset and is assigned to the
safety outputs. The outputs are enabled when all inputs of the safety function
are ACTIVE, the feedback signal is present, and a valid reset operation has
been performed.
Reset
L1 L2
S22
A1
13 23
X4
Machine Control
TIME
X2
A2
14
24
X3
Feedback
K1 K2
OSSD
Table 47 - Configuration 19
Indicator
OUT
IN 1
IN 2
OUT X
IN X
Reset
FB
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
Logic
SMF Level
L3
LOGIC Level
System
K1
SOF Level
K2
M
Function
Configuration ID: 0x62
Safety Functions
IN1
Input Type
GuardLink
Input Type
Not used
Output Type
OSSD
Input Mode
OSSD Disabled
Reset Type
Monitored Manual
Reset Assignment
SOF
IN 1
&
R
FB
OUT X OUT 14/24
Configuration ID: 0x60
IN1
OSSD/EMSS
Not used
OSSD
OSSD Disabled
Monitored Manual
SOF