Chapter 9
440R-ENETR Network Interface Add-on Profile
Table 13 - DG Safety Relay Tags
Name
Data Type
SafetyInput01
BOOL
SafetyInput02
BOOL
PtS12
BOOL
PtS22
BOOL
PtS32
BOOL
PtS42
BOOL
PtS11
BOOL
PtS21
BOOL
PtX1
BOOL
PtX2
BOOL
PtX3
BOOL
PtX4
BOOL
Pt13_14
BOOL
Pt23_24
BOOL
ResetRequired1
BOOL
ResetHeldOn1
BOOL
NonRecoverableFault
BOOL
Fault
BOOL
FaultCode
INT
Config
INT
ValueRotarySwitch
SINT
GuardLink1
AB:GSR_DG_GL:I:0
GuardLink2
AB:GSR_DG_GL:I:0
70
Definition
Safety Input 1 Status - Indicates whether safety input circuit 1 is On or Off.
0 = The input channel is Off.
1 = The input channel is On.
Safety Input 2 Status - Indicates whether safety input circuit 2 is On or Off.
0 = The input channel is Off.
1 = The input channel is On.
S12 Status - Indicates whether terminal S12 of circuit IN01 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
S22 Status - Indicates whether terminal S22 of circuit IN02 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
S32 Status - Indicates whether terminal S32 of circuit IN02 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
S42 Status - Indicates whether terminal S42 of circuit IN02 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
S11 Status - Indicates whether terminal S11 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
S21 Status - Indicates whether terminal S21 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
X1 Status - Indicates whether terminal X1 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
X2 Status - Indicates whether terminal X2 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
X3 Status - Indicates whether terminal X3 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
X4 Status - Indicates whether terminal X4 is On or Off.
0 = The terminal is Off.
1 = The terminal is On.
13/14 Status - Indicates whether output relays contacts at terminals 13/14 are closed or open.
0 = The contacts are open.
1 = The contacts are closed.
23/24 Status - Indicates whether output relays contacts at terminals 23/24 are closed or open.
0 = The contacts are open.
1 = The contacts are closed.
Reset Required Indication - This indication turns On (1) when all monitored input conditions are On and the safety relay Output is
Off (0) on GuardLink circuit 1.
Reset Held On Fault - Indicates that the reset signal for IN1 was held On (1) for longer than the maximum time of 3000 ms.
0 = No fault
1 = Fault
Non-Recoverable Fault Status - Indicates whether the DG safety relay has detected unexpected internal operation.
0 = No fault
1 = Fault
Fault Status - Indicates whether the DG safety relay has detected unexpected operation of a monitored safety device.
0 = No fault
1 = Fault
Fault Code - When a fault occurs, the DG safety relay generates a value to help indicate the potential cause of the fault. See
Table 18 on page 76
for a list of fault codes.
Configuration ID - Each configuration of the DG safety relay has a unique ID. This tag determines if the configuration changed.
Value of Rotary Switch - The DG safety relay provides a unique value of each position of the timer rotary switch.
GuardLink1 Input and Output
GuardLink2 Input and Output
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018