Table 24 - SWS Specifications — DG Safety Relay
Attribute
Wiring terminal
Continuous output current, max
ON state voltage drop (P/S to +), max
Surge output current, max
Surge output current duration, max
Load capacitance, max
Off state leakage current, max
Short circuit detection
Short circuit protection
Galvanic isolation: I/O from logic
Fan-out
(Max number of connections to L11)
Cable length between L11 and L12
Off state leakage current, max
Short circuit detection
Short circuit protection
Table 25 - Safety Output Specifications — DG Safety Relay
Attribute
Wiring terminals
Types
Thermic current I
th
Fuses output (external)
Switched current, min
Switched voltage, min
Mechanical life
Rating
Contact material
Reaction times
Automatic reset
Monitored manual reset
Response time
13/14 and 23/24 safety outputs
SWS output
Recovery time
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
440R-DG2R2T
Output - X2
Input - X1
50 mA
0.2V
700 mA
5 ms
1 µF
< 0.1 mA
No
Yes
No
10
30 m (98.4 ft)
< 0.1 mA
Yes
Yes
440R-DG2R2T
13/14, 23/24
2 N.O.
1 x 6 A
6 A slow blow or 10 A quick blow
10 mA
10V
10,000,000 cycles
UL:C300
AC-15:1.5 A / 250V AC
DC13: 2 A / 24V DC (0.1 Hz)
AgNi + 0.2 µ Au
<100 ms
<500 ms
35 ms
30 ms
100 ms
Specifications
Appendix A
89