Chapter 9
440R-ENETR Network Interface Add-on Profile
Table 15 - 440R-ENETR Interface Input Tags
Name
Data Type
ConnectionFaulted
BOOL
EthernetLink1Sts
BOOL
EthernetLink2Sts
BOOL
OpticalLinkSts
BOOL
OpticalLink2Sts
BOOL
OpticalLink3Sts
BOOL
Relay1Connected
BOOL
Relay2Connected
BOOL
Relay3Connected
BOOL
Relay4Connected
BOOL
Relay5Connected
BOOL
Relay6Connnected
BOOL
72
Table 15
shows the 440R-ENETR interface input tags. These tags are read
only and provide status of the communications to the Ethernet interface.
Definition
Connection Faulted - Indicates whether the connection to the Ethernet interface has faulted.
0 = No connection fault.
1 = Connection has faulted.
Ethernet Link1 Status - Indicates whether Link1 of the Ethernet interface is active.
0 = Link1 is not active.
1 = Link1 is active.
Ethernet Link2 Status - Indicates whether Link2 of the Ethernet interface is active.
0 = Link2 is not active.
1 = Link2 is active.
Optical Link Status - Indicates whether Optical Links from the Ethernet interface to the GSR relays are active.
0 = Optical Link is not active.
1 = Optical Link is not active.
Optical Link2 Status - Indicates whether Optical Link2 from the Ethernet interface to the GSR relays is active.
0 = Optical Link2 is not active.
1 = Optical Link2 is not active.
Optical Link3 Status - Indicates whether Optical Link3 from the Ethernet interface to the GSR relays is active.
0 = Optical Link3 is not active.
1 = Optical Link3 is not active.
Relay 1 Connected - Indicates whether a GSR relay is connected to the Ethernet interface via the optical link.
0 = Relay 1 is not connected.
1 = Relay 1 is connected.
Relay 2 Connected - Indicates whether a GSR relay is connected to the Ethernet interface via the optical link.
0 = Relay 2 is not connected.
1 = Relay 2 is connected.
Relay 3 Connected - Indicates whether a GSR relay is connected to the Ethernet interface via the optical link.
0 = Relay 3 is not connected.
1 = Relay 3 is connected.
Relay 4 Connected - Indicates whether a GSR relay is connected to the Ethernet interface via the optical link.
0 = Relay 4 is not connected.
1 = Relay 4 is connected.
Relay 5 Connected - Indicates whether a GSR relay is connected to the Ethernet interface via the optical link.
0 = Relay 5 is not connected.
1 = Relay 5 is connected.
Relay 6 Connected - Indicates whether a GSR relay is connected to the Ethernet interface via the optical link.
0 = Relay 6 is not connected.
1 = Relay 6 is connected.
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018