Delay Setting; Verification - Allen-Bradley Guardmaster GuardLink User Manual

Safety system
Table of Contents

Advertisement

Delay Setting

Verification

The delay is set by the 16 position switch as described in
inputs must be opened during the delay. If the inputs close before the
expiration of the delay time, the delayed output remains ON and any locked
guards remain locked. If the inputs are reopened the timer restarts from zero.
Table 9 - Delay Switch Settings
Position
Delay
0
Immediate
1
100 ms
2
200 ms
3
300 ms
4
500 ms
5
1 s
6
1.5 s
7
2 s
Table 10
shows how the status indicators confirm the delay setting. The
bottom three indicators flash at 1 Hz. The flashing pauses for four seconds and
then repeats. The number of flashes is equal to the delay switch setting.
Table 10 - Indicators Confirm Delay Setting
Indicator
Color
PWR/Fault
OUT
IN 1
IN 2
OUT X
IN X
Reset
FB
You can verify the configuration of the DG safety relay in three ways:
• The push buttons on the front of the DG safety relay
• The 440R-ENETR interface web page
• The Add-on-profile (AOP) in the Studio 5000 environment
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
Position
Delay
8
3 s
9
5 s
10
8 s
11
10 s
12
15 s
13
20 s
14
25 s
15
30 s
Status
Configuration mode
The number of flashes
indicates the delay switch
setting. For example:
0 = no flashing
5 = five flashes
Configuration
Chapter 5
Table
9. The DG
53