Chapter 5
Configuration
Sel./Save Push Button
Reset
Configuration Steps
50
Configuration Mode
When you are in the configuration mode, the duration that the Config/Set
button is depressed determines what the DG safety relay reveals.
Button Press
Function
Short
You can cycle through the configuration and can switch between the function of the blinking
indicator. See
Long
Abort the changes; you leave the configuration mode without saving the changes. The PWR/
Fault indicator flashes green at a 1 Hz rate. Upon release, the indicators revert to the wiring
terminal status.
Run Mode
Button Press
Function
Short
The status indicators display the following:
• Alternating flashing green indicators if optical buses are active.
• Alternating flashing red indicators if optical buses are inactive.
Long
Nothing happens.
Configuration Mode
Button Press
Function
Short
You can jump from one configuration step to the next.
Long
The new configuration is saved.
If you press both push buttons simultaneously for longer than three seconds,
the DG safety relay performs a power cycle. The same can be accomplished if
you remove and reapply power to terminal A1.
Before starting to configure the DG safety relay, review the configuration
functions in
Table
8. The configuration examples in
select the correct configuration.
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
Table 8
for indicator descriptions.
Appendix B
help you