Chapter 5
Configuration
52
4. Short press the Config/Set button to change the function on the IN 2
status indicator, if available.
Short press the Sel./Save button to accept and go to the next step.
5. Short press the Config/Set button to change the function on the
OUT X status indicator.
Short press the Sel./Save button to accept and go to the next step.
6. Short press the Config/Set button to change the function on the IN X
status indicator.
Short press the Sel./Save button to accept and go to the next step.
7. Short press the Config/Set button to change the function on the Reset
status indicator.
Short press the Sel./Save button to accept and go to the next step.
8. Short press the Config/Set button to change the function on the FB
status indicator.
Short press the Sel./Save button to accept and go to the next step.
9. All indicators flash the new configuration. Use this step to confirm your
configuration.
Short press the Sel./Save button to accept and go to the next step.
10. Now, you can verify and adjust the time delay. If the rotary switch is at
position 0, all indicators (except the PWR/Fault) are off. If the rotary
switch is in a position other than 0, then the bottom three indicators
flash. The number of times the indicators flash is equal to the Time
switch position.
11. Rotate the rotary switch to the desired off-delay setting (see
page
53).
12. When the configuration is finished, long press the Sel./Save button to
save the new configuration.
The status indicators flash their configuration while the button is held
down. When the button is released, the PWR/Fault status indicator
flashes green twice, turns solid red for about five seconds, and then turns
solid green again. Now, the other status indicators reflect the status of
the wiring terminals (see
IMPORTANT To abort the configuration without saving your settings:
• Long press the Config/Set button, then short press the Config/Set
button. The DG safety relay returns to normal operation (Run mode)
without saving the changes.
• Wait longer than 60 seconds without any additional changes.
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
Table 11 on page
55).
Table 9 on