Chapter 5
Configuration
54

Push Buttons on the Front of DG Safety Relay

While in the Run mode, short presses of the Config/Set button can verify the
configuration.
IMPORTANT The PWR/Fault indicator remains green through these steps.
1. Short press the Config/Set push button.
The indicators show the configuration. Compare the colors of each
indicator to your desired colors.
2. Short press the Config/Set push button again.
The indicators show the Time switch setting. If the indicators are off,
then the TIME is set to zero. For a setting other than zero, the bottom
three indicators flash green. The number of flashes is equal to the switch
setting. The flashing pauses for four seconds and then repeats.
3. Short press the Config/Set push button one last time to return to the
running status indication.

AOP in the Studio 5000 Environment

Each configuration is assigned a unique identification. The ID appears as a
decimal value in the Config field in the Controller Tags. See
Examples on page 80
for more information. After the initial configuration,
record the Config value. This value can then be compared in the future to
detect changes.
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018