Status
Indicator
Function
OUT
Number of Safety Functions
IN 1
Input Type IN1
IN 2
Input Type IN2
OUT X
Output Type
IN X
Input Mode
Reset
Reset Type
FB
Reset Assignment
(1) Only available if Manual Monitored Reset is selected.
Table 8 - Configuration
Indicator Color and Setting
Activate two Safety Functions
(IN1 and IN2)
Activate GuardLink Input
function on IN1
Activate GuardLink Input
function on IN2
Activate SWS Output on X2
Activate SWS or OSSD Input on
X1, depends on the previous
step (SWS Input if OUT X is SWS
Out, OSSD In out if OUT X is
OSSD.)
Manual Monitored Reset
Reset on the Output function
1. Long press the Config/Set button.
The PWR/Fault indicator turns green and all other indicators flash red
quickly, which indicates that the DG safety relay is in Configuration
mode. Shortly after release of the Config/Set button:
• The PWR/Fault status indicator flashes green at 1 Hz.
• The OUT status indicator flashes the current configuration (red or
green) at 1 Hz.
• The remaining status indicators are solid red, solid green, or off.
2. Short press the Config/Set button to change the function of the OUT
status indicator.
IMPORTANT If you press the Config/Set button in these steps again, the status
Short press the Sel./Save button to accept and go to the next step.
3. Short press the Config/Set button to change the function on the IN 1
status indicator.
Short press the Sel./Save button to accept and go to the next step.
IMPORTANT If the IN 2 indicator is off, the function is not available in this
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
Indicator Color and Setting
Activate one Safety Function
(only IN1)
Activate OSSD or EMSS Input
function on IN1
Activate OSSD or EMSS Input
function on IN1
Activate OSSD Output on X2
Disable Input on X1
Automatic Reset
(1)
Reset only on IN 1
indicator switches back and forth between red and green.
configuration. The configuration proceeds to the OUT X indicator -
go to
step
5.
Configuration
Chapter 5
Indicator Color and Setting
If only one Safety Function (IN1)
is selected, the IN2 is disabled
Not used if Automatic Reset is
selected