Table 16 - Ethernet Output Tags for Relay 1
Name
Data Type
Reset
BOOL
FaultReset
BOOL
GuardLink1
AB:GSR_DG_GL:O:0
GuardLink1.UnlockCmd
DINT
GuardLink1.LockCmd
DINT
GuardLink1.FaultResetCmd
DINT
GuardLink2
AB:GSR_DG_GL:O:0
Table 17 - DG Safety Relay Fault Codes
Fault Codes
Type
0x0001
Recoverable
0x0002
Recoverable
0x0003
Recoverable
0x0004
Non-recoverable
0x0006
Non-recoverable
0x000A
Non-recoverable
0x000D
Recoverable
0x0010
Non-recoverable
0x0011
Non-recoverable
0x0013
Non-recoverable
0x0015
Non-recoverable
0x0017
Non-recoverable
0x0040
Recoverable
0x0041
Recoverable
0x0042
Recoverable
0x0043
Recoverable
0x0044
Recoverable
0x0045
Recoverable
0x0101
Recoverable
0x0102
Recoverable
0x0103
Recoverable
0x0104
Recoverable
0x0105
Recoverable
0x0106
Recoverable
The Ethernet interface can send commands to each of the relays that are
included in the opto-links.
DG safety relay. Output tags for other GSR relays can be found in publication
440R-UM009.
Definition
Reset 1 - Applies a reset command to the inputs to input IN1.
0 = Clears the reset.
1 = Initiates a reset.
Fault Reset - Applies a reset command to the DG safety relay when a faulted state exists.
0 = Clears the reset.
1 = Initiates a reset.
GuardLink1 - This field contains three commands (Lock, Unlock, and Fault Reset) that can be sent to the GuardLink1
circuit of the DG safety relay.
Unlock Command - Can be used to send unlock commands to one or more guard locking interlocks.
Lock Command - Can be used to send lock commands to one or more guard locking interlocks.
Fault Reset Command - Can be used to send fault reset commands to one or more guard locking interlocks. This tag must
be used when the guard locking interlock has faulted. The command cycles power to the interlock.
GuardLink2 - This field contains three commands (Lock, Unlock, and Fault Reset) that can be sent to the GuardLink2
circuit of the DG safety relay. See the description for GuardLink1.
Table 17
lists the fault codes for the DG safety relay.
Name
Test Out A stuck at
Test Out B stuck at
Power Fault
VCC Fault
Internal hard fault
Relay Contacts End of Life
Test Out Cross Fault
Terminal Fault S11
Terminal Fault S21
Terminal Fault S22
Terminal Fault S42
Terminal Fault X2
GuardLink-CH[0] no Termination
GuardLink-CH[1] no Termination
GuardLink-CH[0] not wired
GuardLink-CH[1] not wired
GuardLink-CH[0] more than 32 slave devices
GuardLink-CH[1] more than 32 slave devices
GuardLink-CH[0] Tap 1 communication error
GuardLink-CH[0] Tap 2 communication error
GuardLink-CH[0] Tap 3 communication error
GuardLink-CH[0] Tap 4 communication error
GuardLink-CH[0] Tap 5 communication error
GuardLink-CH[0] Tap 6 communication error
Rockwell Automation Publication 440R-UM015C-EN-P - April 2018
440R-ENETR Network Interface Add-on Profile
Table 16
lists the tags for Relay 1, where Relay 1 is a
Description
Stuck @ 24V S11
Stuck @ 24V S21
A1 is over 27V and under 20V
3.3V is out of range
Summary of all faults
Force guided relay feedback error
Shortcut between S11 and S21
Terminal issue when configured as output like Test Out A
Terminal issue when configured as output like Test Out B
Terminal issue when configured as Guardlink
Terminal issue when configured as Guardlink
Terminal issue when configured as OSSD/SWS
No terminator detected
No terminator detected
No IAH responses
No IAH responses
More than 32 slave devices
More than 32 slave devices
No, or corrupted, communication
No, or corrupted, communication
No, or corrupted, communication
No, or corrupted, communication
No, or corrupted, communication
No, or corrupted, communication